Plan Review Notes For Permit 18030173 |
Permit Number |
18030173 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-12 15:36:16 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY PERSON | | RESPONSIBLE FOR THE DESIGN. PER 107.2.1.4, QUALITY OF | | BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A | | MINIMUM 1/8 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR | | OTHER ACCEPTABLE MEDIUM. THIS POLICY MAY INCLUDE SUCH | | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR | | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. FS 481.229; | | FBC 107.2.1, 107.3.5 | | 2. VALUE OF STATED WORK APPEARS LOW. PROVIDE COPY OF | | SIGNED CONTRACT WITH SCOPE AND VALUE OF WORK, TO | | INCLUDE ALL MATERIALS AND LABOR. FBC 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|