Plan Review Notes
Plan Review Notes For Permit 18030167
Permit Number 18030167
Review Stop E
Sequence Number 2
Notes
Date Text
2018-04-27 13:01:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. RISER SHOWS THAT PANEL EP-2 IS FED FROM PANEL EP-1,
 BUT THE PANEL SCHEDULE FOR EP-1 DOES NOT SHOW ANY FEED
 TO THIS PANEL OR THE LOAD ASSOCIATED WITH IT. PROVIDE
 CORRECTION. FBC 107.2.1 (PANELS ARE NOW NAMED
 DIFFERENTLY, BUT THE PANEL SCHEDULES ARE NOT SUPPLIED
 FOR THE PANELS SHOWN, AND THE LOAD FOR EACH PANEL IS
 NOT DETAILED. PROVIDE COMPLETED PANEL SCHEDULES WITH
 LOADS FOR THE PANELS TO CONFIRM THE PANELS ARE NOT
 OVERLOADED.)
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.)
 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1 (NOT PROVIDED. A NOTE THAT STATES ALL
 NON-ESSENTIAL OUTLETS TO BE TIME CLOCK CONTROLLED IS
 NOT SUFFICIENT. THE EXCEPTION NOTED IN RESPONSE LETTER
 IS ONLY FOR RECEPTACLES DESIGNATED FOR EQUIPMENT THAT
 REQUIRES CONTINUOUS OPERATION. SHOW ON PLAN WHICH
 RECEPTACLES WILL BE TIME CLOCK CONTROLLED, IN
 COMPLIANCE WITH ABOVE REQUIREMENT.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  