2018-04-27 13:01:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED. |
| 5. RISER SHOWS THAT PANEL EP-2 IS FED FROM PANEL EP-1, |
| BUT THE PANEL SCHEDULE FOR EP-1 DOES NOT SHOW ANY FEED |
| TO THIS PANEL OR THE LOAD ASSOCIATED WITH IT. PROVIDE |
| CORRECTION. FBC 107.2.1 (PANELS ARE NOW NAMED |
| DIFFERENTLY, BUT THE PANEL SCHEDULES ARE NOT SUPPLIED |
| FOR THE PANELS SHOWN, AND THE LOAD FOR EACH PANEL IS |
| NOT DETAILED. PROVIDE COMPLETED PANEL SCHEDULES WITH |
| LOADS FOR THE PANELS TO CONFIRM THE PANELS ARE NOT |
| OVERLOADED.) |
| 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.) |
| 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| EC C405.6.1 (NOT PROVIDED. A NOTE THAT STATES ALL |
| NON-ESSENTIAL OUTLETS TO BE TIME CLOCK CONTROLLED IS |
| NOT SUFFICIENT. THE EXCEPTION NOTED IN RESPONSE LETTER |
| IS ONLY FOR RECEPTACLES DESIGNATED FOR EQUIPMENT THAT |
| REQUIRES CONTINUOUS OPERATION. SHOW ON PLAN WHICH |
| RECEPTACLES WILL BE TIME CLOCK CONTROLLED, IN |
| COMPLIANCE WITH ABOVE REQUIREMENT.) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |