Plan Review Notes For Permit 18030167 |
Permit Number |
18030167 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-16 07:57:11 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18030167 | | 3/16/17 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET MEP-1: REFER TO SECTION 809.2 FBC-14 EXISTING | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | CALCULATIONS FOR ALL ALTERED ROOMS AND SPACES PER TABLE | | 403.3.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT | | INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR | | AIR. | | | | 2) MEP-1: FLEX DUCT CANNOT BE USED FOR THE TOILET ROOM | | EXHAUST PER UL AND MANUFACTURER'S SPECIFICATIONS. | | PROVIDE METAL DUCTWORK PER SMACNA STANDARDS. | | | | 3) MEP-1: CLARIFY IF THE EF-1 FANS ARE NEW OR EXISTING. | | PROVIDE EQUIPMENT SCHEDULES FOR NEW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|