Plan Review Notes
Plan Review Notes For Permit 18030167
Permit Number 18030167
Review Stop M
Sequence Number 1
Notes
Date Text
2018-03-16 07:57:111ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18030167
 3/16/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MEP-1: REFER TO SECTION 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ALTERED ROOMS AND SPACES PER TABLE
 403.3.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) MEP-1: FLEX DUCT CANNOT BE USED FOR THE TOILET ROOM
 EXHAUST PER UL AND MANUFACTURER'S SPECIFICATIONS.
 PROVIDE METAL DUCTWORK PER SMACNA STANDARDS.
  
 3) MEP-1: CLARIFY IF THE EF-1 FANS ARE NEW OR EXISTING.
 PROVIDE EQUIPMENT SCHEDULES FOR NEW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  