2018-03-22 14:49:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL NOTE 1 AND 17 ON SHEETS CS-1 AND MEP 1
 THROUGH 4 STATE THAT THE 2011 NEC IS USED FOR DESIGN.
 THIS IS NOT THE CURRENT CODE IN EFFECT. PROVIDE
 CORRECTIONS. FBC PREFACE
 2. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES IN
 KITCHEN. NEC 210.8(B)(2)
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
 4. PANELS ARE SHOWN AS 3?, 120/240 VOLT, WHICH WOULD
 HAVE B? AS A HIGH LEG. HOWEVER, THE PANEL SCHEDULES
 SHOWS 120 VOLT LOADS ON B?. PROVIDE CLARIFICATION
 AND/OR CORRECTION. FBC 107.2.1
 5. RISER SHOWS THAT PANEL EP-2 IS FED FROM PANEL EP-1,
 BUT THE PANEL SCHEDULE FOR EP-1 DOES NOT SHOW ANY FEED
 TO THIS PANEL OR THE LOAD ASSOCIATED WITH IT. PROVIDE
 CORRECTION. FBC 107.2.1
 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  