2018-03-22 14:49:27 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL NOTE 1 AND 17 ON SHEETS CS-1 AND MEP 1 |
| THROUGH 4 STATE THAT THE 2011 NEC IS USED FOR DESIGN. |
| THIS IS NOT THE CURRENT CODE IN EFFECT. PROVIDE |
| CORRECTIONS. FBC PREFACE |
| 2. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES IN |
| KITCHEN. NEC 210.8(B)(2) |
| 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| PRESENT. WPB FBC 105.1, 107.2.1 |
| 4. PANELS ARE SHOWN AS 3?, 120/240 VOLT, WHICH WOULD |
| HAVE B? AS A HIGH LEG. HOWEVER, THE PANEL SCHEDULES |
| SHOWS 120 VOLT LOADS ON B?. PROVIDE CLARIFICATION |
| AND/OR CORRECTION. FBC 107.2.1 |
| 5. RISER SHOWS THAT PANEL EP-2 IS FED FROM PANEL EP-1, |
| BUT THE PANEL SCHEDULE FOR EP-1 DOES NOT SHOW ANY FEED |
| TO THIS PANEL OR THE LOAD ASSOCIATED WITH IT. PROVIDE |
| CORRECTION. FBC 107.2.1 |
| 6. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 7. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| EC C405.6.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |
| |