2018-03-09 13:55:37 | ****PLAN REVIEW COMMENTS**** |
| |
| ART LANGE BUILDING PLANS EXAMINER |
| |
| DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33402 |
| 561-805-6718 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 1. ON BATHROOM DOORS 4 AND 5 DO THEY HAVE DOOR |
| CLOSURES? IT IS NOT SHOWN ON THE DOOR SCHEDULE. |
| |
| IF A CLOSURE IS PROVIDED SHOW A 12 INCH CLEARANCE AT |
| THE LATCH PULL SIDE OF THE DOOR. |
| |
| ACCESSIBILITY 404.2.4 MANEUVERING CLEARANCES. |
| |
| MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL |
| COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL |
| EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED |
| LATCH SIDE OR HINGE SIDE CLEARANCE. |
| DOORS AT THE CARE SUITES AND THE ATTACHED BATHROOMS |
| SHALL HAVE A CLEAR DISTANCE ON THE LATCH PUSH SIDE OF |
| THE DOOR OF A MINIMUM OF 12 INCHES. SEE FLORIDA |
| ACCESSIBILITY CODE FIGURE 404.2.4.1 DETAIL (C). |
| |
| 2. STAFF ROOM 110 APPEARS TO BE ABOUT 5 FT 3 INCHED |
| WIDE. THE MINIMUM ROOM WIDTH IS 7 FT. |
| FBC 1208.1 MINIMUM ROOM WIDTHS. |
| HABITABLE SPACES, OTHER THAN A KITCHEN, SHALL BE NOT |
| LESS THAN 7 FEET (2134 MM) IN ANY PLAN DIMENSION. |
| |
| |
| WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| THE PERMIT PACKAGE. |
| |
| A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| |