2018-03-09 10:18:10 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. SHEET E-1 DOES NOT SHOW LOCATION OF PANEL B. PROVIDE | | CORRECTION. FBC 107.2.1 | | 2. PANEL MDP IS NOW SHOWN AS A "FUTURE PANEL". IF THIS | | IS FUTURE, HOW ARE ALL OF THE LOADS IN THE PANEL | | SCHEDULE FOR THIS PANEL BEING FED? NOTES FROM FINAL | | INSPECTION THAT FAILED STATE THAT THE ORIGINAL | | DISCONNECT SHOWN ON PLAN WAS NOT REPLACED WITH A PANEL | | AS ORIGINALLY SHOWN ON PLANS. PLAN NEEDS TO ACCURATELY | | REFLECT INSTALLATION. CLARIFY AND/OR CORRECT. FBC | | 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|