2018-03-09 10:18:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHEET E-1 DOES NOT SHOW LOCATION OF PANEL B. PROVIDE
 CORRECTION. FBC 107.2.1
 2. PANEL MDP IS NOW SHOWN AS A "FUTURE PANEL". IF THIS
 IS FUTURE, HOW ARE ALL OF THE LOADS IN THE PANEL
 SCHEDULE FOR THIS PANEL BEING FED? NOTES FROM FINAL
 INSPECTION THAT FAILED STATE THAT THE ORIGINAL
 DISCONNECT SHOWN ON PLAN WAS NOT REPLACED WITH A PANEL
 AS ORIGINALLY SHOWN ON PLANS. PLAN NEEDS TO ACCURATELY
 REFLECT INSTALLATION. CLARIFY AND/OR CORRECT. FBC
 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  