2019-06-26 12:28:014TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18030157
 6/26/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.0: THE RHEEM AC EQUIPMENT MODELS IN THE
 SCHEDULE ARE STRAIGHT COOL SYSTEMS PER THE
 MANUFACTURER'S SPECIFICATIONS, HOWEWER THE COMCHECK
 ENERGY COMPLIANCE REPORT LISTS THEM AS HEAT PUMPS.
 PLEASE CORRECT THE DATA AND REMOVE THE HSPF RATINGS
 WHICH ARE NOT RELEVANT TO THE SYSTEMS. EFFICIENCIES FOR
 THE SYSTEMS ARE RATED IN SEER FOR SYSTEMS #1, 2, 3, &
 5, AND EER FOR THE 10-TON SYSTEM #4. PLEASE NOTE THAT
 TWO SIGNED AND SEALED COPIES BY THE ENGINEER OF RECORD
 ARE REQUIRED- SECTION 107/.2.1 WPB.
  
 2) AS PREVIOUSLY REQUESTED TWO COMPLETE SETS OF SIGNED
 AND SEALED AC CALCULATIONS ARE REQUIRED. CURRENTLY ONLY
 CALCULATIONS FOR SYSTEMS #1 & 2 HAVE BEEN PROVIDED.
 PLEASE NOTE THAT THE CURRENT CALCULATIONS SHOW NO HEAT
 GAIN FOM VENTILATION AIR WHICH MUST BE INCLUDED AND
 SHOWN IN THE RESUBMITTED CALCULATIONS- SECTION 107.2.1
 WPB.
  
 3) M2.0: THE AC EQUIPMENT SCHEDULE IS INDICATING ONLY
 2000 CFMS FOR THE AHU-4, HOWEVER THE MANUFACTURER'S
 SPECIFICATIONS INDICATE 4000 CFMS NOMINAL FOR THE UNIT-
 RHGL-120.
  
 4) M1.0: THE REVISED AC PLAN IS NOW SHOWING O/A TO BE
 DUCTED THROUGH THE EXTERIOR WALLS USING INTERIOR FANS,
 HOWEVER THE EQUIPMENT SCHEDULE IS INDICATING ROOF
 MOUNTED FANS- GREENHECK SAF. PLEASE CORRECT AND NOTE
 THAT THE O/A OPENINGS IN THE EXTERIOR WALLS MUST BE
 PROTECTED WITH CORROSION-RESISTENT SCREENS, LOUVERS, OR
 GRILLES- SECTION 401.5 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  