2019-04-25 10:49:303RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18030157
 4/25/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.0: COMMENT #7 FROM THE 2ND REVIEW STILL
 EXISTS- PLEASE COMPLY.7) M-1.0: DUCT SMOKE DETECTORS
 ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE 5-TON AHU'S
 PER SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN
 EXEMPTION CAN BE APPLIED FOR THE 5-TON SYSTEMS IF THE
 MANUFACTURER'S SPECIFICATIONS INDICATE THOSE SYSTEMS
 ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR.
  
 2) SHEET M2.0: THE RHEEM AC EQUIPMENT MODELS IN THE
 SCHEDULE ARE STRAIGHT COOL SYSTEMS PER THE
 MANUFACTURER'S SPECIFICATIONS, HOWEVWER THE COMCHECK
 ENERGY COMPLIANCE REPORT LISTS THEM AS HEAT PUMPS-
 PLEASE CORRECT. PLEASE NOTE THAT THE AC SCHEDULE
 INDICATES THE AIR HANDLERS ARE NOT EQUIPPED WITH HEAT
 STRIPS, HOWEVER MINIMUM HEAT IS REQUIRED FOR ALL
 OCCUPIED SPACES- SECTION 309.1 FBC M.
  
 3) COMMENT #3 FROM THE 2ND REVIEW STILL PARTIALLY
 EXISTS. THE ELITE HVAC CALCS HAVE NOT BEEN PROVIDED
 WITH AN ORIGINAL SEAL AND SIGNATURE BY THE EOR. 3)
 ENGINEER'S SEAL ON THE COMCHECK FORM AND THE ELITE HVAC
 CALCS IS A COPIED, REDUCED IN SIZE INK SEAL. PROVIDE
 ORIGINAL 1-7/8" DIAMETER SEALS AND WET SIGNATURES ON
 THE DOCUMENTS- SECTION 61G15-23.002 (2) FAC.
  
 4) PLEASE NOTE THAT THE AC CALCULATIONS ARE INDICATING
 ONLY TWO AIR HANDLERS- 1 & 2, HOWEVER THERE ARE 5 AIR
 HANDLERS IN THE SPACE.
  
 5) COMMENT #8 FROM THE 2ND REVIEW STILL EXISTS- PLEASE
 COMPLY. 8) M-1:0: PROVIDE AN EQUIPMENT SCHEDULE ON THE
 PLAN FOR THE CLASSIC CL-2250 FAN, AND PROVIDE INPACT
 PROTECTION AND WIND LOAD ENGINEERING FOR INSTALLATION-
 SECTION 301.15 FBC M.
  
 6) M-2.0: THE DETAIL PROVIDED FOR THE O/A ROOF FAN
 INSTALLATIONS USING A 6" DUCT EXTENSION ABOVE THE ROOF
 DOES NOT APPEAR TO BE APPLICABLE FOR THE SPECIFIED
 GREENHECK SAF FANS. THESE TYES OF ROOF FANS ARE
 TYPICALLY MOUNTED ON PRE-MANUFACTURED CURBS PER THE
 MANUFACTURER'S SPECIFICATIONS AND PER THE PRODUCT
 APPROVALS OR NOA'S. PLEASE SUBMIT THE SPECS AND THE
 NOA'S.
  
 7) M-2.0: THE NEW AIR BALANCE SCHEDULE INDICATES
 GREATER AMOUNTS OF RETURN AIR TO THE SYSTEMS THAN THE
 AMOUNTS OF SUPPLY AIR PROVIDED? PLEASE SEE SECTION
 601.5 (3) FBC M AND CORRECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER