2019-04-25 10:49:30 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #18030157 |
| 4/25/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-1.0: COMMENT #7 FROM THE 2ND REVIEW STILL |
| EXISTS- PLEASE COMPLY.7) M-1.0: DUCT SMOKE DETECTORS |
| ARE REQUIRED IN THE SUPPLY SYSTEMS OF THE 5-TON AHU'S |
| PER SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN |
| EXEMPTION CAN BE APPLIED FOR THE 5-TON SYSTEMS IF THE |
| MANUFACTURER'S SPECIFICATIONS INDICATE THOSE SYSTEMS |
| ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY |
| AIR. |
| |
| 2) SHEET M2.0: THE RHEEM AC EQUIPMENT MODELS IN THE |
| SCHEDULE ARE STRAIGHT COOL SYSTEMS PER THE |
| MANUFACTURER'S SPECIFICATIONS, HOWEVWER THE COMCHECK |
| ENERGY COMPLIANCE REPORT LISTS THEM AS HEAT PUMPS- |
| PLEASE CORRECT. PLEASE NOTE THAT THE AC SCHEDULE |
| INDICATES THE AIR HANDLERS ARE NOT EQUIPPED WITH HEAT |
| STRIPS, HOWEVER MINIMUM HEAT IS REQUIRED FOR ALL |
| OCCUPIED SPACES- SECTION 309.1 FBC M. |
| |
| 3) COMMENT #3 FROM THE 2ND REVIEW STILL PARTIALLY |
| EXISTS. THE ELITE HVAC CALCS HAVE NOT BEEN PROVIDED |
| WITH AN ORIGINAL SEAL AND SIGNATURE BY THE EOR. 3) |
| ENGINEER'S SEAL ON THE COMCHECK FORM AND THE ELITE HVAC |
| CALCS IS A COPIED, REDUCED IN SIZE INK SEAL. PROVIDE |
| ORIGINAL 1-7/8" DIAMETER SEALS AND WET SIGNATURES ON |
| THE DOCUMENTS- SECTION 61G15-23.002 (2) FAC. |
| |
| 4) PLEASE NOTE THAT THE AC CALCULATIONS ARE INDICATING |
| ONLY TWO AIR HANDLERS- 1 & 2, HOWEVER THERE ARE 5 AIR |
| HANDLERS IN THE SPACE. |
| |
| 5) COMMENT #8 FROM THE 2ND REVIEW STILL EXISTS- PLEASE |
| COMPLY. 8) M-1:0: PROVIDE AN EQUIPMENT SCHEDULE ON THE |
| PLAN FOR THE CLASSIC CL-2250 FAN, AND PROVIDE INPACT |
| PROTECTION AND WIND LOAD ENGINEERING FOR INSTALLATION- |
| SECTION 301.15 FBC M. |
| |
| 6) M-2.0: THE DETAIL PROVIDED FOR THE O/A ROOF FAN |
| INSTALLATIONS USING A 6" DUCT EXTENSION ABOVE THE ROOF |
| DOES NOT APPEAR TO BE APPLICABLE FOR THE SPECIFIED |
| GREENHECK SAF FANS. THESE TYES OF ROOF FANS ARE |
| TYPICALLY MOUNTED ON PRE-MANUFACTURED CURBS PER THE |
| MANUFACTURER'S SPECIFICATIONS AND PER THE PRODUCT |
| APPROVALS OR NOA'S. PLEASE SUBMIT THE SPECS AND THE |
| NOA'S. |
| |
| 7) M-2.0: THE NEW AIR BALANCE SCHEDULE INDICATES |
| GREATER AMOUNTS OF RETURN AIR TO THE SYSTEMS THAN THE |
| AMOUNTS OF SUPPLY AIR PROVIDED? PLEASE SEE SECTION |
| 601.5 (3) FBC M AND CORRECT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |