2019-04-29 15:34:04 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. THERE ARE TWO DIFFERENT RISER DIAGRAMS PROVIDED WITH |
| CONFLICTING INFORMATION. PROVIDE CORRECTION. NEC 215.5; |
| WPB FBC 107.2.1 (THE PERMIT APPLICATION STATES THE WORK |
| FOR THIS PLAN IS FOR 925 RAILROAD. THE ELECTRICAL PLAN |
| SHOULD ONLY INCLUDE INFORMATION FOR WORK AT THAT |
| ADDRESS. WHY ARE 2 SEPARATE RISER DIAGRAMS INCLUDED? |
| PROVIDE CLARIFICATION AND/OR REMOVE INFORMATION NOT |
| PERTINENT TO THIS PERMIT APPLICAITON.SOME SHEETS STATE |
| THE WORK IS FOR 925 ADDRESS, SOME SHEETS STATE THE WORK |
| IS FOR 925/1013, BUT THE FLOOR PLANS DO NOT INDICATE |
| WHICH ADDRESS OR WHERE EXACTLY THE WORK IS TO BE |
| PERFORMED.) |
| 2. THE LOAD CALCULATION PROVIDED DOES NOT RECONCILE |
| WITH INFORMATION PROVIDED ON PANEL SCHEDULES. PROVIDE |
| CORRECTION SO LOAD FOR EACH AREA IS DETAILED CORRECTLY. |
| NEC 220; WPB FBC 107.2.1(NOT CORRECTED. LOAD |
| CALCULATION ON SHEET E2.0 STATES THE LOAD IS 440.59 |
| AMPS, WHILE THE PANEL SCHEDULE FOR THE SAME SERVICE |
| STATES THE LOAD AS 251 AMPS. PROVIDE CORRECTION AS |
| PREVIOUSLY REQUESTED.) |
| 3. CORRECTED. |
| 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. THE CURRENT |
| INFORMATION PROVIDED SHOWS THE AMPERAGE LOAD OF |
| LIGHTING, THIS IS NOT ACCEPTABLE FOR CODE COMPLIANCE. |
| SEE CODE SECTION FOR DETAILS. FBC EC C405.4.2 (NOT |
| PROVIDED.) |
| 5. THERE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THIS |
| PLAN THAT IS CONFLICTING AND/OR MISSING. A FULL REVIEW |
| IS NOT POSSIBLE AT THIS TIME. FURTHER COMMENTS MAY BE |
| NECESSARY UPON NEXT REVIEW. WPB FBC 107.2.1(COMMENT |
| STILL APPLIES.) |
| |
| NEW COMMENT: |
| |
| 6. FOR NEW SERVICE ON SHEET E2.0, PROVIDE AVAILABLE |
| SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING |
| INFORMATION FROM THE POWER COMPANY STATING WHAT THE |
| AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO |
| CONFIRM THE AIC RATING OF THE SERVICE EQUIPMENT IS |
| ADEQUATE. PROVIDE AIC RATING OF ELECTRICAL PANELS.NEC |
| 110.9, 110.10 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |