Plan Review Notes
Plan Review Notes For Permit 18030157
Permit Number 18030157
Review Stop E
Sequence Number 3
Notes
Date Text
2019-04-29 15:34:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. THERE ARE TWO DIFFERENT RISER DIAGRAMS PROVIDED WITH
 CONFLICTING INFORMATION. PROVIDE CORRECTION. NEC 215.5;
 WPB FBC 107.2.1 (THE PERMIT APPLICATION STATES THE WORK
 FOR THIS PLAN IS FOR 925 RAILROAD. THE ELECTRICAL PLAN
 SHOULD ONLY INCLUDE INFORMATION FOR WORK AT THAT
 ADDRESS. WHY ARE 2 SEPARATE RISER DIAGRAMS INCLUDED?
 PROVIDE CLARIFICATION AND/OR REMOVE INFORMATION NOT
 PERTINENT TO THIS PERMIT APPLICAITON.SOME SHEETS STATE
 THE WORK IS FOR 925 ADDRESS, SOME SHEETS STATE THE WORK
 IS FOR 925/1013, BUT THE FLOOR PLANS DO NOT INDICATE
 WHICH ADDRESS OR WHERE EXACTLY THE WORK IS TO BE
 PERFORMED.)
 2. THE LOAD CALCULATION PROVIDED DOES NOT RECONCILE
 WITH INFORMATION PROVIDED ON PANEL SCHEDULES. PROVIDE
 CORRECTION SO LOAD FOR EACH AREA IS DETAILED CORRECTLY.
 NEC 220; WPB FBC 107.2.1(NOT CORRECTED. LOAD
 CALCULATION ON SHEET E2.0 STATES THE LOAD IS 440.59
 AMPS, WHILE THE PANEL SCHEDULE FOR THE SAME SERVICE
 STATES THE LOAD AS 251 AMPS. PROVIDE CORRECTION AS
 PREVIOUSLY REQUESTED.)
 3. CORRECTED.
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. THE CURRENT
 INFORMATION PROVIDED SHOWS THE AMPERAGE LOAD OF
 LIGHTING, THIS IS NOT ACCEPTABLE FOR CODE COMPLIANCE.
 SEE CODE SECTION FOR DETAILS. FBC EC C405.4.2 (NOT
 PROVIDED.)
 5. THERE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THIS
 PLAN THAT IS CONFLICTING AND/OR MISSING. A FULL REVIEW
 IS NOT POSSIBLE AT THIS TIME. FURTHER COMMENTS MAY BE
 NECESSARY UPON NEXT REVIEW. WPB FBC 107.2.1(COMMENT
 STILL APPLIES.)
  
 NEW COMMENT:
  
 6. FOR NEW SERVICE ON SHEET E2.0, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE AIC RATING OF THE SERVICE EQUIPMENT IS
 ADEQUATE. PROVIDE AIC RATING OF ELECTRICAL PANELS.NEC
 110.9, 110.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  