Plan Review Notes
Plan Review Notes For Permit 18030157
Permit Number 18030157
Review Stop B
Sequence Number 3
Notes
Date Text
2018-08-28 12:05:05BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SCOPE OF WORK HAS CHANGED DUE TO THE CHANGE OF
 OCCUPANCY. ADDITIONAL REVIEWS REQUIRED - MECH.,
 ELECTRICAL, PLUMBING AND ZONING.
 FBC EXISTING SEC. 1001.2.2 CHANGE OF OCCUPANCY
 CLASSIFICATION OR GROUP.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 2. CHANGE CLASSIFICATION OF WORK ON PLAN PAGE CV-1.0
 FROM ALTERATION LEVEL II TO CHANGE OF OCCUPANCY. NEW
 CLASSIFICATION SHOULD BE A-3 GALLERY.
 303.4 ASSEMBLY GROUP A-3.
 GROUP A-3 OCCUPANCY INCLUDES ASSEMBLY USES INTENDED FOR
 WORSHIP, RECREATION OR AMUSEMENT AND OTHER ASSEMBLY
 USES NOT CLASSIFIED ELSEWHERE IN GROUP A INCLUDING, BUT
 NOT LIMITED TO:
 ART GALLERIES
  
 3. APPLICABLE BUILDING CODES ON PLAN PAGE C-1 ARE
 INCORRECT. CURRENT GOVERNING CODE IS THE 2017 FBC
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 4. DRAWING SCHEDULE ON PLAN PAGE C-1 IS INCORRECT.
 COVER SHEET IS CV-1.0. SITE PLAN IS C-1.
  
 5. DRAWING SCALE ON PLAN PAGES A-1, A-2 AND A-3 IS TOO
 SMALL. MINIMUM SCALE IS 1/8" = 1 FOOT.
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 6. MINIMUM NUMBER OF PLUMBING FACILITIES SHALL COMPLY
 WITH FBC CHPT. 29.
 FBC 2902.1 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED IN THE MINIMUM
 NUMBER AS SHOWN IN TABLE 2902.1 BASED ON THE ACTUAL USE
 OF THE BUILDING OR SPACE. USES NOT SHOWN IN TABLE
 2902.1 SHALL BE CONSIDERED INDIVIDUALLY BY THE CODE
 OFFICIAL. THE NUMBER OF OCCUPANTS SHALL BE DETERMINED
 BY THIS CODE.
  
 7. REFERENCE PLAN PAGE S-1.0 FOR THE FOLLOWING
 COMMENTS.
 7A. PROVIDE DESIGN WIND LOADS FOR CONTAINERS.
 ENGINEERING TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL.
 7B. PROVIDE DESIGN FOR FOUNDATION. IF EXISTING, PROVIDE
 CERTIFICATION BY A DESIGN PROFESSIONAL.
 7C. PROVIDE ATTACHMENT DETAIL FOR CONTAINER TO
 FOUNDATION.
 7D. PROVIDE WELD SPECIFICATIONS.
 7E. PROVIDE WELDER CERTIFICATIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  