 2ND REVIEW: DENIED
 PLUMBING COMMENTS
 1. PLAN SHEET P-2.0:
 A. MINIMUM PLUMBING FIXTURE REQUIREMENTS FOR OCCUPANCY
 LOAD 378 MERCANTILE IS INCORRECT. REQUIRES TWO (2) EACH
 TOILETS, TWO (2) EACH LAVATORIES, ONE (1) EACH SERVICE
 SINK AND ONE (1) EACH DRINKING FOUNTAIN PER FBC PL
 TABLE 403.1. CORRECT ON PLANS PER WPB FBC 107.2.1
 B. EXISTING WOMEN?S TOILET ROOM DOES NOT MEET THE
 REQUIREMENTS OF FBC ACC 604.8.1.7. PLEASE NOTE ADVISORY
 604.8.1.6 LAVATORY AND 604.8.Y WHICH NOTES THAT THE
 FLORIDA REQUIREMENT ONLY APPLIES TO NEW CONSTRUCTION,
 THEY ARE DESIRABLE FOR ALL WHEELCHAIR ACCESSIBLE
 COMPARTMENTS AND SHOULD BE CONSIDERED WHERE FEASIBLE.
 PER FBC ACC 202.4.1 DISPROPORTIONATE COST UP TO 20% (IN
 THIS CASE $5000.00) OF THE PROJECT COST SHALL BE USED
 TO UPGRADE ACCESSIBILITY REQUIREMENTS. PROVIDE
 COMPLIANCE TO FBC ACC 604.8.1.7 OR SHOW INFEASIBILITY
 OF PROVIDING THE UPGRADE WHICH WOULD INCLUDE BUT NOT BE
 LIMITED TO EXCEEDING THE 20% COST. PROVIDE
 DOCUMENTATION FOR THE SAME PER WPB FBC 107.2.1.
 C. ONE EACH (1) VTR (VENT THROUGH THE ROOF OR TO THE
 OUTSIDE) IS REQUIRED FOR EACH BUILDING DRAIN PER FBC PL
 904.1. SANITARY RISER DIAGRAM NOTES ONE (1) EACH
 EXISTING VTR/SV ABOVE CEILING AND TWO (2) EACH NEW
 VTR/SV ABOVE CEILING. WHAT IS THE DEFINITION OF THE
 TERM ?SV?. PER WPB FBC 107.2.1, PLEASE CLARIFY ON PLANS
 AND SHOW THAT AT LEAST ONE OF THE VENTS DOES INDEED
 EXTEND TO THE OUTSIDE.
 D. THE WATER CLOSET IS TO BE SUPPLIED WITH COLD WATER
 ONLY FOR FLUSHING PURPOSES. CORRECT ON WATER RISER
 DIAGRAM PER WPB FBC 107.2.1.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715