2019-02-20 09:30:46 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18030157 |
| 2/20/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS.THE |
| $10,000 JOB VALUE FOR THE SCOPE OF WORK SHOWN ON THE |
| PLANS IS LOW- SEE SECTION 109.3 WPB AND PROVIDE AN |
| ACCURATE JOB VALUE. |
| |
| 2) ENGINEER'S TITLE BLOCK MISSING FROM THE MEP PLANS- |
| SECTION 61G15-23.002 FAC. |
| |
| 3) ENGINEER'S SEAL ON THE COMCHECK FORM AND THE ELITE |
| HVAC CALCS IS A COPIED, REDUCED IN SIZE INK SEAL. |
| PROVIDE ORIGINAL 1-7/8" DIAMETER SEALS AND WET |
| SIGNATURES ON THE DOCUMENTS- SECTION 61G15-23.002 (2) |
| FAC. |
| |
| 4) SHEET M-1.0: THE PROPOSED MECHANICAL PLAN SHALL BE |
| DRAWN TO A MINIMUM 1/8" = 1'0" SCALE PER SECTION |
| 107.2.1.3 WPB. THE SCALE OF THE PLAN IS LISTED AS 3/32 |
| AT THE BOTTOM OF THE PLAN, HOWEVER LISTED AS 3/16" IN |
| THE MARGIN. PLEASE NOTE THAT MUCH OF THE PRINT ON THE |
| PRINT IS TOO SMALL TO READ DUE TO THE REDUCED SCALE |
| SIZE. |
| |
| 5) THE COMCHECK REPORT IS MISSING ENVELOPE DATA FOR THE |
| WEST SIDE OF THE BUILDING WHERE THE NEW STOREFRONT |
| GLASS AND WALLS WERE INSTALLED TO ENCLOSED THE GARAGE |
| BAYS. THESE ENCLOSURES ARE DEFINED AS ADDITIONS PER |
| SECTION 202 FBC EC. THE REPORT IS ALSO LACKING ANY DATA |
| FOR THE MECHANICAL SYSTEMS. PLEASE PROVIDE A COMPLETE |
| REPORT- SECTION 107.1 WPB. |
| |
| 6) SHEET M-1.0: PROVIDE VENTILATION CALCULATIONS PER SF |
| FOR ALL ROOMS AND SPACES TO VERIFY THE AMOUNTS OF O/A |
| TO BE PROVIDED BY THE EXISTING SYSTEMS- SEE TABLE |
| 403.3.1.1 FBC M. |
| |
| 7) M-1.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| SUPPLY SYSTEMS OF THE AHU'S PER SECTION 606.2.1 FBC M. |
| PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED FOR THE |
| 5-TON SYSTEMS IF THE MANUFACTURER'S SPECIFICATIONS |
| INDICATE THOSE SYSTEMS ARE NOT CAPABLE OF PRODUCING |
| OVER 2000 CFMS OF SUPPLY AIR. |
| |
| 8) M-1:0: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR |
| THE CLASSIC CL-2250 FAN, AND PROVIDE INPACT PROTECTION |
| AND WIND LOAD ENGINEERING FOR INSTALLATION- SECTION |
| 301.15 FBC M. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |