Plan Review Notes
Plan Review Notes For Permit 18030157
Permit Number 18030157
Review Stop M
Sequence Number 2
Notes
Date Text
2019-02-20 09:30:462ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18030157
 2/20/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENT #1 FROM THE 1ST REVIEW STILL EXISTS.THE
 $10,000 JOB VALUE FOR THE SCOPE OF WORK SHOWN ON THE
 PLANS IS LOW- SEE SECTION 109.3 WPB AND PROVIDE AN
 ACCURATE JOB VALUE.
  
 2) ENGINEER'S TITLE BLOCK MISSING FROM THE MEP PLANS-
 SECTION 61G15-23.002 FAC.
  
 3) ENGINEER'S SEAL ON THE COMCHECK FORM AND THE ELITE
 HVAC CALCS IS A COPIED, REDUCED IN SIZE INK SEAL.
 PROVIDE ORIGINAL 1-7/8" DIAMETER SEALS AND WET
 SIGNATURES ON THE DOCUMENTS- SECTION 61G15-23.002 (2)
 FAC.
  
 4) SHEET M-1.0: THE PROPOSED MECHANICAL PLAN SHALL BE
 DRAWN TO A MINIMUM 1/8" = 1'0" SCALE PER SECTION
 107.2.1.3 WPB. THE SCALE OF THE PLAN IS LISTED AS 3/32
 AT THE BOTTOM OF THE PLAN, HOWEVER LISTED AS 3/16" IN
 THE MARGIN. PLEASE NOTE THAT MUCH OF THE PRINT ON THE
 PRINT IS TOO SMALL TO READ DUE TO THE REDUCED SCALE
 SIZE.
  
 5) THE COMCHECK REPORT IS MISSING ENVELOPE DATA FOR THE
 WEST SIDE OF THE BUILDING WHERE THE NEW STOREFRONT
 GLASS AND WALLS WERE INSTALLED TO ENCLOSED THE GARAGE
 BAYS. THESE ENCLOSURES ARE DEFINED AS ADDITIONS PER
 SECTION 202 FBC EC. THE REPORT IS ALSO LACKING ANY DATA
 FOR THE MECHANICAL SYSTEMS. PLEASE PROVIDE A COMPLETE
 REPORT- SECTION 107.1 WPB.
  
 6) SHEET M-1.0: PROVIDE VENTILATION CALCULATIONS PER SF
 FOR ALL ROOMS AND SPACES TO VERIFY THE AMOUNTS OF O/A
 TO BE PROVIDED BY THE EXISTING SYSTEMS- SEE TABLE
 403.3.1.1 FBC M.
  
 7) M-1.0: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF THE AHU'S PER SECTION 606.2.1 FBC M.
 PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED FOR THE
 5-TON SYSTEMS IF THE MANUFACTURER'S SPECIFICATIONS
 INDICATE THOSE SYSTEMS ARE NOT CAPABLE OF PRODUCING
 OVER 2000 CFMS OF SUPPLY AIR.
  
 8) M-1:0: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR
 THE CLASSIC CL-2250 FAN, AND PROVIDE INPACT PROTECTION
 AND WIND LOAD ENGINEERING FOR INSTALLATION- SECTION
 301.15 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  