2019-02-25 14:15:51 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THERE ARE TWO DIFFERENT RISER DIAGRAMS PROVIDED WITH |
| CONFLICTING INFORMATION. PROVIDE CORRECTION. NEC 215.5; |
| WPB FBC 107.2.1 |
| 2. THE LOAD CALCULATION PROVIDED DOES NOT RECONCILE |
| WITH INFORMATION PROVIDED ON PANEL SCHEDULES. PROVIDE |
| CORRECTION SO LOAD FOR EACH AREA IS DETAILED CORRECTLY. |
| NEC 220; WPB FBC 107.2.1 |
| 3. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. THE CURRENT |
| INFORMATION PROVIDED SHOWS THE AMPERAGE LOAD OF |
| LIGHTING, THIS IS NOT ACCEPTABLE FOR CODE COMPLIANCE. |
| SEE CODE SECTION FOR DETAILS. FBC EC C405.4.2 |
| 5. THERE IS A SUBSTANTIAL AMOUNT OF INFORMATION ON THIS |
| PLAN THAT IS CONFLICTING AND/OR MISSING. A FULL REVIEW |
| IS NOT POSSIBLE AT THIS TIME. FURTHER COMMENTS MAY BE |
| NECESSARY UPON NEXT REVIEW. WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |