Date |
Text |
2018-07-13 08:10:12 | THE CITY HAS BEEN REQUESTING AN OVERALL SITE PLAN FOR |
| THIS PROJECT IN ORDER TO ASSIGN OCCUPANCIES, FIRE |
| SEPARATION DISTANCES, BUILDING HEIGHT AND USE FOR THE |
| VARIOUS PIECES AND PARTS THAT ARE PRESENT ON THE SITE. |
| TO DATE, A FULL AND COMPRHENSIVE SITE PLAN HAS YET BE |
| TO BE PRESENTED. THIS HAS PREVENTED US FROM COMPLETING |
| A COMPREHENSIVE REVIEW. THE WORK MAY BE PHASED OR |
| STAGED TO VARIOUS COMPONENTS OF THE PROJECT ONCE THE |
| OVERALL PROJECT IS DEFINED, CLEARLY STATED, SHOWN ON A |
| DIMENSIONED SITE PLAN AND APPROVED FOR THE USES THAT |
| ARE BEING REQUESTED. BOTH FIRE AND PLANNING/ZONING NEED |
| TO REVIEW THE MIXED USE OF THIS PROPERTY AND APPROVE |
| THE USES IN THE LOCATIONS THAT ARE REQUESTED. AT THIS |
| TIME, IT IS BELIEVED THERE ARE GOUP B, BUSINESS USE(S), |
| GROUP S, STORAGE USE(S), GROUP A, ASSEMBLY USE(S) AND |
| POSSIBLY OTHERS. UNTIL AN OVERALL OCCUPANT LOAD, USE |
| AND LIMITS OF PROPERTY ARE DETERMINED AND DEFINED, IT |
| IS NOT POSSIBLE TO COMPLETE A REVIEW OF THE PROJECT. |
| |
| THE PLANS SUBMITTED UNDER TJHIS REQUEST ARE MISSING |
| IMPORTANT AND VALUABLE INFORMATION NEEDED FOR THE |
| REVIEW. THOSE ITEMS INCLUDE, BUT ARE NOT LIMITED TO: |
| OVERALL SITE PLAN |
| USE OF THE PROPERTY |
| OCCUPANT LOAD FOR EACH PORTION AND USE |
| WIND LOAD CALCULATIONS AND AFFIRMATION OF COMPLIANCE |
| WELDING PROCEDURE SPECIFICATION (WPS) |
| WELDERS CERTIFICATIONS |
| COMPLETE LAYOUT INCLUDING LIMITS OF MIXED USES |
| COMPLETE AND COMPREHENSIVE LIFE SAFETY PLAN |
| SPRINKLER PLANS |
| ALL OTHER REQUIRED INFORMATION BY FLORIDA BUILDING CODE |
| - BUILDING SECTION 107 |
| |
| REVIEW IS UNABLE TO BE COMPLETED UNTIL ALL REQUIRED AND |
| PREVIOUSLY REQUESTED INFORMATION IS PROVIDED. |
| |
| DOUGLAS HARVEY |
| ASSISTANT BUILDING OFFICIAL |
| [email protected] |
| 561-805-6740 |
| |