2018-07-13 08:10:12THE CITY HAS BEEN REQUESTING AN OVERALL SITE PLAN FOR
 THIS PROJECT IN ORDER TO ASSIGN OCCUPANCIES, FIRE
 SEPARATION DISTANCES, BUILDING HEIGHT AND USE FOR THE
 VARIOUS PIECES AND PARTS THAT ARE PRESENT ON THE SITE.
 TO DATE, A FULL AND COMPRHENSIVE SITE PLAN HAS YET BE
 TO BE PRESENTED. THIS HAS PREVENTED US FROM COMPLETING
 A COMPREHENSIVE REVIEW. THE WORK MAY BE PHASED OR
 STAGED TO VARIOUS COMPONENTS OF THE PROJECT ONCE THE
 OVERALL PROJECT IS DEFINED, CLEARLY STATED, SHOWN ON A
 DIMENSIONED SITE PLAN AND APPROVED FOR THE USES THAT
 ARE BEING REQUESTED. BOTH FIRE AND PLANNING/ZONING NEED
 TO REVIEW THE MIXED USE OF THIS PROPERTY AND APPROVE
 THE USES IN THE LOCATIONS THAT ARE REQUESTED. AT THIS
 TIME, IT IS BELIEVED THERE ARE GOUP B, BUSINESS USE(S),
 GROUP S, STORAGE USE(S), GROUP A, ASSEMBLY USE(S) AND
 POSSIBLY OTHERS. UNTIL AN OVERALL OCCUPANT LOAD, USE
 AND LIMITS OF PROPERTY ARE DETERMINED AND DEFINED, IT
 IS NOT POSSIBLE TO COMPLETE A REVIEW OF THE PROJECT.
  
 THE PLANS SUBMITTED UNDER TJHIS REQUEST ARE MISSING
 IMPORTANT AND VALUABLE INFORMATION NEEDED FOR THE
 REVIEW. THOSE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
 OVERALL SITE PLAN
 USE OF THE PROPERTY
 OCCUPANT LOAD FOR EACH PORTION AND USE
 WIND LOAD CALCULATIONS AND AFFIRMATION OF COMPLIANCE
 WELDING PROCEDURE SPECIFICATION (WPS)
 WELDERS CERTIFICATIONS
 COMPLETE LAYOUT INCLUDING LIMITS OF MIXED USES
 COMPLETE AND COMPREHENSIVE LIFE SAFETY PLAN
 SPRINKLER PLANS
 ALL OTHER REQUIRED INFORMATION BY FLORIDA BUILDING CODE
 - BUILDING SECTION 107
  
 REVIEW IS UNABLE TO BE COMPLETED UNTIL ALL REQUIRED AND
 PREVIOUSLY REQUESTED INFORMATION IS PROVIDED.
  