2018-09-13 12:42:24 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18030157 |
| 9/13/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE $10,000.00 JOB VALUE LISTED ON THE PERMIT |
| APPLICATION APPEARS TO BE VERY LOW FOR A 13,798 S.F. |
| REMODEL AND CHANGE OF OCCUPANCY, WHICH INCLUDES AMONG |
| OTHER THINGS A NEW ACCESSIBLE BATHROOM, A NEW HANDICAP |
| RAMP, AND NEW ADDITIONS (LOADING BAY CONVERSIONS) |
| PLEASE REFER TO SECTION 109.3 WPB AND PROVIDE DETAILED |
| ESTIMATES, AND/OR BONA FIDE CONTRACTS FOR ALL PHASES OF |
| THE PROJECT INCLUDING STRUCTURAL, ARCHITECTURAL, |
| MECHANICAL, ELECTRICAL, PLUMBING, INTERIOR AND EXTERIOR |
| FINISH WORK, SITE WORK, DESIGN FEES, AND OVERHEAD AND |
| PROFIT. THE TOTAL VALUE SHALL INCLUDE LABOR, MATERIALS, |
| EQUIPMENT AND APPLIANCES. |
| |
| 2) THE PROJECT INFORMATION, INDEX, ETC. ON COVER SHEET |
| CV-1.0 DESIGNED BY CALITO P.E. DOES NOT MATCH THE REST |
| OF THE PLANS IN THE SET THAT ARE DESIGNED BY GOUBRAN |
| ARCHITECT. PLEASE CORRECT OR REMOVE THE SHEET FROM THE |
| SETS. |
| |
| 3) SHEET M-1: THE O/A CALCULATIONS ARE INCORRECTLY |
| IDENTIFYING THE LARGE 11,376 S.F. GALLERY AREAS AS |
| SALES. PLEASE SEE TABLE 403.3.1.1 FBC M AND PROVIDE |
| CALCULATIONS FOR THE GALLERIES BASED ON AN OCCUPANT |
| DENSITY OF 40 PERSONS PER 100 S.F./7.5 CFMS PER PERSON |
| + 0,06 CFMS PER S.F. ADJUST THE TABLE TO SHOW THE |
| REQUIRED AND PROVIDED CFMS OF OUTSIDE AIR FOR ALL ROOMS |
| AND AREAS. |
| |
| 4) M-1: INDICATE HOW THE LARGE STORAGE ROOM ON THE |
| SOUTH SIDE OF THE OCCUPANCY IS BEING VENTILATED- TABLE |
| 403.3.1.1 FBC M. |
| |
| 5) M-1: A MINIMUM 10' CLEARANCE DISTANCE TO THE |
| DRIVEWAY IS REQUIRED FOR THE O/A FAN THAT IS PROVIDING |
| FAN TO THE ART STORAGE ROOM ON THE NORTH SIDE- SECTION |
| 401.4 FBC M. THIS REQUIREMENT WILL REMAIN UNTIL THE |
| PLAN ACTUALLY SHOWS THE DRIVEWAY WILL BE REMOVED AND |
| CONVERTED TO NON-VEHICULAR USE. |
| |
| 6) M-1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE ART |
| STORAGE FAN AND INDICATE HOW THE NEW WALL OPENING WILL |
| PROTECTED AGAINST WIND AND RAIN- SECTION 401.5. PLEASE |
| NOTE THAT OUTDOOR AIR INTAKE OPENINGS LOCATED IN |
| EXTERIOR WALLS SHALL MEET THE PROVISIONS FOR EXTERIOR |
| WALL OPENING PROTECTIVES IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 7) M-1: THE NEW AIR CONDITIONED DISPLAY AREAS THAT WERE |
| PREVIOUSLY LOADING DOCKS ARE DEFINED AS ADDITIONS PER |
| SECTION C202 FBC EC. PROVIDE AC LOAD CALCULATIONS IN |
| ACCODANCE WITH SECTION C403.2.1 FBC EC. |
| |
| 8) M-1: NEW ADDITIONS AND SPACES THAT CHANGE OCCUPANCY |
| ARE SUBJECT TO COMPLIANCE WITH THE CURRENT FBC EC. |
| PLEASE SEE SECTION C101.5.1 AND SUBMIT A COMPLIANCE |
| REPORT USIBNG APPROVED SOFTWARE. REFER TO THE FOLLOWING |
| SECTIONS FOR MORE INFORMATION - C503.2, C101.3, AND |
| C401.2. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. PLEASE NOTE THAT |
| SUBMITTAL OF CORRECTED PLANS MAY RESULT IN NEW PLAN |
| REVIEW COMMENTS. |
| |