Plan Review Notes For Permit 18030154 |
Permit Number |
18030154 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-03-21 09:06:39 | 2ND REVIEW FBC-2017 MECHANICAL | | REVISION PERMIT #18030154 | | 3/21/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE ORIGINAL INCREASE IN VALUE OF $14,750.00 | | APPARENTLY DID NOT INCLUDE THE RTU-2 REPLACEMENT, WHICH | | IS NOW BEING SHOWN ON THE SECOND PLAN SUBMITTAL. PLEASE | | INCREASE THE VALUE ACCORDINGLY- SECTION 109.3 WEST PALM | | BEACH AMENDMENTS TO THE FBC-17. | | | | 2) PROVIDE COMPLETE WIND LOAD ENGINEERING FOR | | ATTACHMENT OF THE RTU TO THE EXISTING CURB. IF A CURB | | ADAPTER IS REQUIRED PLEASE INCLUDE THE ATTACHMENT IN | | THE ENGINEERING , AND SUBMIT A CUT SHEET FROM THE | | MANUFACTURER- SECTION 301.15. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|