Plan Review Notes
Plan Review Notes For Permit 18030154
Permit Number 18030154
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-12 14:27:142014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 18030154
 W. P. B. PERMIT: 17070327
 ADD: 1885 OKEECHOBEE BLVD. / SUITE 1885
 CONT: DUKE INDIANA CONSTRUCTION
 TEL: 954-453-5261
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 12/ 2018
 ACTION: DENIED
  
 1) THE REVISION INDICATES AN INCREASED VALUE OF
 $14,750.00 IN VALUE. THIS INCREASE SEEMS LOW, ALSO WORK
 NOT SHOWN AS A REVISION (DELTA):
  
 1A) SHEET A200 NOTE 11 INDICATES ONLY 2 TO REMOVE THE
 EDGE OF THE DOCK LEVELERS WHERE REQUIRED FOR DOCK BAYS
 11-15.
  
 1B) SHEET A201 DOES NOT SHOW NEW WORK ON THE RAMP FOR
 BAYS 12-15.
  
 1C) SHEET A201 THE WALL LEGEND SHOWS NEW WALLS TO THE
 UNDERSIDE OF THE CEILING, THE PLANS SHOWS (2) NEW SUCH
 WALLS AND A COUNTER TOP.
  
 108.3* BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE UNDER
 ESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE TOTAL REPLACEMENT PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRICAL,
 PLUMBING, MECHANICAL, INTERIOR FINISHES, NORMAL SITE
 WORK (EXCAVATION AND BACKFILL FOR BUILDINGS),
 ARCHITECTURAL AND DESIGN FEES, MARKETING COST, OVERHEAD
 AND PROFIT; EXCLUDING ONLY LAND VALUE. VALUATION
 REFERENCES MAY INCLUDE THE LATEST PUBLISHED DATA OF
 NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) SHEET A300 SHOWS VARIOUS DETAILS:
  
 2A) DETAIL B3 THE BACK WALL OF THE WATER CLOSET SHOWS
 THE BACK GRAB BAR ONLY 4 INCHES FROM THE CORNER, THIS
 ONLY WORKS IF YOU INSTALL THE WATER CLOSET 16 INCHES
 FROM THE SIDE WALL.
 2014 ACCESS. CODE. 604.5.2 REAR WALL. THE REAR WALL
 GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND EXTEND
 FROM THE CENTERLINE OF THE WATER CLOSET 12 INCHES
 MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE OTHER
 SIDE.
  
 2B) DETAIL B3. THE REAR AND SIDE GRAB BAR DETAILS SHOW
 THE GRAB BARS BEING DIMENSIONED FROM THE CENTERLINE TO
 THE FINISH FLOOR. PLEASE NOTE THE GRAB BARS ARE TO BE
 MEASURED FROM THE TOP OF THE GRASPING SURFACE TO FINISH
 FLOOR. SEE 2014 ACCESS. CODE SECTION 609.4. 33 TO 36
 INCHES FROM FINISH FLOOR.
  
 2C) DETAIL D3. THE TOILET PAPER DISPENSERS, SHOWS
 COMPLIANCE FOR THE HEIGHT BUT NOT THE HORIZONTAL
 DIMENSION FROM THE FRONT OF THE WATER CLOSET SHALL BE 7
 TO 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. 2014
 ACCESS. CODE 604.7.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  