2018-05-15 14:14:41 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. VALUE LISTED FOR THE ADDITIONAL WORK SHOWN ON PLAN |
| APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT FOR |
| ADDITIONAL WORK TO INCLUDE SCOPE AND VALUE OF WORK |
| INCLUDING MATERIALS AND LABOR. FBC 109.3 (NOT |
| PROVIDED.) |
| 3. PROVIDE TWO COPIES OF PLAN WITH SIGNATURE OF PERSON |
| RESPONSIBLE FOR DESIGN ON EACH PLAN. A PHOTOCOPIED |
| SIGNATURE IS NOT ACCEPTABLE. FBC 107.1; FS 471.025, |
| 471.003, 481.229 (NOT PROVIDED.) |
| 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE |
| E3706.2, E3902 (NOT PROVIDED.) |
| 5. PROVIDE AFCI PROTECTION PER CODE: ?BRANCH CIRCUITS |
| THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, DINING |
| ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED.? A NOTE WILL SUFFICE. NEC |
| 210.12; FBC RE E3902.16 (NOT PROVIDED.) |
| 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 (NOT PROVIDED.) |
| 7. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8; FBC RE E3902.6 (NOT |
| PROVIDED.) |
| 8. PROVIDE GFCI PROTECTION FOR DISHWASHER IF |
| APPLICABLE. NEC 210.8(D); FBC RE E3902.10 (NOT |
| PROVIDED.) |
| 9. IT APPEARS THE LOCATION OF THE NEW PANEL ON ORIGINAL |
| PLAN IS LOCATED IN THE KITCHEN. BE ADVISED THAT |
| CONDUCTORS FROM METER CAN TO FIRST MEANS OF DISCONNECT |
| ARE NOT PERMITTED TO EXTEND FARTHER THAN 8 FEET FROM |
| THE METER WITHOUT OVERCURRENT PROTECTION. IF THE FEED |
| IS UNDERGROUND AS SHOWN ON THE ORIGINAL PLAN, THIS |
| WOULD BE ACCEPTABLE. HOWEVER, IF THE FEED MUST RUN |
| THROUGH THE STRUCTURE, A MAIN DISCONNECT WILL BE |
| REQUIRED ON THE EXTERIOR OF THE HOUSE. CLARIFY AND/OR |
| CORRECT. NEC 230.70; FBC RE E3601.6 (NOT PROVIDED.) |
| 10. PROVIDE SMOKE ALARMS IN EACH LOCATION REQUIRED PER |
| CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE |
| EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC |
| R314.3, FBC 107.2.1 (NOT PROVIDED.) |
| 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 (NOT |
| PROVIDED.) |
| 12. SEVERAL AREAS DO NOT COMPLY WITH THE WALL SPACING |
| REQUIREMENTS FOR OUTLETS. RECEPTACLES SHALL BE |
| INSTALLED SO THAT NO POINT MEASURED HORIZONTALLY ALONG |
| THE FLOOR LINE OF ANY WALL SPACE IS MORE THAN 6 FEET |
| FROM A RECEPTACLE OUTLET, EXCEPT FOR KITCHENS WHICH |
| REQUIRE THAT RECEPTACLE OUTLETS SHALL BE INSTALLED SO |
| THAT NO POINT ALONG THE WALL LINE IS MORE THAN 24 |
| INCHES MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET |
| IN THAT SPACE. A MINIMUM OF TWO 20 AMP CIRCUITS ARE |
| REQUIRED FOR COUNTER OUTLETS IN KITCHEN. PROVIDE |
| CORRECTIONS. NEC 210.11, 210.52; FBC RE E3901.2.1, |
| E3901.4 (NOT PROVIDED.) |
| 13. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE |
| E3703.4, E3901.6 (NOT PROVIDED.) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |
| |