2018-12-06 09:40:28PERMIT # 18030117
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 3RD REVIEW - FAIL COMMENTS
  
 1) REPEAT COMMENT (3RD TIME): PER NFPA 101, CHAPTER 30
 - NEW APARTMENTS
 30.3.5.1: ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
 PLEASE PROVIDE DRAWING NOTE INDICATING COMPLIANCE OF
 THIS REQUIREMENT, OR PROVIDE JUSTIFICATION.
  
 2) REPEAT COMMENT (2ND TIME): A 1-HOUR FIRE RATED
 SEPERATION IS PROVIDED BETWEEN THE TWO BOTTOM UNITS,
 HOWEVER THE SEPERATION BETWEEN THE TOP AND BOTTOM UNITS
 IS NOT PROVIDED.
 PLEASE PROVIDE THE SEPERATION, IF ANY, BETWEEN THE TOP
 AND BOTTOM UNITS.
  
 3) SHEETS A-1 & A-2: THE FIRE RATED WALL IS MARKED AND
 IDENTIFIED, HOWEVER, THE FIRE RATING FOR THE FLOOR THAT
 SEPERATES THE TOP AND BOTTOM STORIES IS NOT PROVIDED.
  
 4) A LAWN SPRINKLER DRAWING IS PROVIDED, HOWEVER THIS
 DOES NOT APPLY TO COMMENT #1. A LAWN SPRINKLER SYSTEM
 IS NOT THE SAME AS A FIRE SPRINKLER SYSTEM.
  
  