Plan Review Notes
Plan Review Notes For Permit 18030117
Permit Number 18030117
Review Stop P
Sequence Number 2
Notes
Date Text
2018-06-06 14:13:142ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED
  
 1. PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.3.5.1.3
  
 3. PLACE NOTE ON PLAN PIPES MAY NEED TO BE EXPOSED FOR
 INSPECTION UP TO THE DISCRETION OF THE FIELD INSPECTOR.
 PER FBC PL 312
  
 NEW COMMENTS:
  
 1. THE LAVATORY,S NOT NOT APPEAR TO HAVE THE REQUIRED
 21" INFRONT OF FIXTURE PER FBC PL 405.3.1
  
 2. SHT. A.02 THE PIPING FOR THE NEW KITCHEN SHALL NOT
 CONNECT TO THE WET VENT OF THE BATHROOM PER FBC PL
 912.1
  
 3. PLEASE INDICATE ON THE PLAN LOCATION OF THE WATER
 HEATER AND MARK THE FIXTURE AS NEW OR EXISTING. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  