2018-05-07 14:48:48PERMIT # 18030117
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW -
  
 1) REPEAT COMMENT: PER NFPA 101, CHAPTER 30 - NEW
 APARTMENTS
 30.3.5.1: ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM.
 PLEASE PROVIDE DRAWING NOTE INDICATING COMPLIANCE OF
 THIS REQUIREMENT, OR PROVIDE JUSTIFICATION.
  
 2) A 1-HOUR FIRE RATED SEPERATION IS PROVIDED BETWEEN
 THE TWO BOTTOM UNITS, HOWEVER THE SEPERATION BETWEEN
 THE TOP AND BOTTOM UNITS IS NOT PROVIDED.
 PLEASE PROVIDE THE SEPERATION, IF ANY, BETWEEN THE TOP
 AND BOTTOM UNITS.
  
  
 THANK YOU,