2018-06-07 08:44:45 | 2ND REVIEW: FBC 2017 5TH EDITION |
| FBC 2017 EXISTING BUILDING |
| |
| UNDER REVIEW |
| |
| 5/18/18 MET WITH OWNER, EXPLAINED FIRST REVIEW COMMENTS |
| OF 4/18/18 WERE NOT SUFFIENTLY ADDRESSED. |
| |
| FIRST REVIEW COMMENTS SEE BELOW: |
| |
| AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA |
| EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE |
| SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY |
| PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY |
| A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964. |
| THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO |
| CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM |
| WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE |
| RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING |
| AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM |
| MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED |
| SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF |
| A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE |
| RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE |
| PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT |
| ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY |
| ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I |
| PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR |
| CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE |
| EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO |
| VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY |
| ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW |
| DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT |
| APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A |
| LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC |
| 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. |
| THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING |
| THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS |
| PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE |
| FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL |
| CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL |
| PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN |
| ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER |
| 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS |
| INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE |
| ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND |
| A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE |
| EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF |
| THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017 |
| EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR |
| TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE |
| REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE |
| DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL |
| NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW |
| WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE |
| REQUIRED. |
| |
| THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE |
| MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND |
| THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW |
| CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS |
| COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT |
| TO CHANGE. |
| |
| |
| STEVEN KENNEDY, CBO |
| ASSISTANT BUILDING OFFICIAL |
| (561) 805-6710 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 5TH EDITION |
| 1ST REVIEW FBC 2017 EXISTING BUILDING |
| |
| |
| AS DISCUSSED WITH ARCHITECT NORM PAUL, I PROVIDED VIA |
| EMAIL THE FILE RECORD REGARDING THE BUILDING AT THE |
| SUBJECT ADDRESS. IT ESTABLISHES THAT THE SINGLE STORY |
| PORTION SHOWN AS A THIRD UNIT ON THE PROPERTY WAS ONLY |
| A ROOM WITH A BATHROOM AND A ONE CAR GARAGE IN 1964. |
| THERE IS NO PERMIT RECORD ON FILE THAT I CAN FIND TO |
| CHANGE THAT AREA OF APPROXIMATELY 605 SF FROM A ROOM |
| WITH BATH AND GARAGE TO A DWELLING UNIT. THERE ARE |
| RECORDS FOR OTHER WORK SUCH AS RECENT WINDOW, ROOFING |
| AND ELECTRICAL UPGRADES. THE WINDOW SERVING THE BEDROOM |
| MAY NOT MEET EGRESS REQUIREMENTS. SUCH PERMITS ISSUED |
| SEPARATELY DO NOT ALLOW FOR THE LEGAL ESTABLISHMENT OF |
| A THIRD UNIT. THE UNIT MAY APPEAR LEGAL BUT AGAIN, THE |
| RECORD TO LEGALLY ESTABLISH IT IS NOT APPARENT. THE |
| PRESUMPTION IS THAT WORK WAS DONE IN THE PAST WITHOUT |
| ALL THE REQUIRED PERMITTING TO PROPERLY AND LEGALLY |
| ESTABLISH THE USE OF THE APPARENT THIRD UNIT. I |
| PROVIDED THE CONTACT INFORMATION TO THE CUSTOMER FOR |
| CRAIG MCPHERSON, CUSTOMER SERVICE ASSOCIATE IN THE |
| EVENT THEY MAY WISH TO REQUEST HE CHECK RECORDS TO |
| VERIFY MY CONCLUSION. TO PROCEED WITH LEGALLY |
| ESTABLISHING THE THIRD UNIT, THE APPLICANT MUST NOW |
| DEVELOP A PLAN TO DEMONSTRATE COMPLIANCE WITH CURRENT |
| APPLICABLE CODE AS IF CHANGING THE LAYOUT ON FILE TO A |
| LEGAL DWELLING UNIT UNDER THE REQUIREMENTS OF THE FBC |
| 2017 EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. |
| THE PLAN MUST SHOW COMPLIANCE WITH PLUMBING REGARDING |
| THE CONNECTIONS TO THE KITCHEN AS THE BATHROOM IS |
| PRESUMED TO BE EXISTING, COMPLETE ELECTRICAL COMPLIANCE |
| FOR THE INTERIOR IN TERMS OF REQUIRED ELECTRICAL |
| CIRCUITS, DEVICES AND SMOKE ALARMS, ETC, A MECHANICAL |
| PLAN FOR REQUIRED HEAT AND ANY PROVIDED COOLING, AND AN |
| ENERGY SUBMITTAL. ADDITIONALLY COMPLIANCE WITH CHAPTER |
| 9 FBC IS REQUIRED AS TO FIRE PROTECTION SYSTEMS |
| INCLUDING INCLUDING FIRE SPRINKLER AND FIRE ALARM. THE |
| ARCHITECTURAL PLAN MUST PROVIDE THE CODE REFERENCE AND |
| A SCOPE OF WORK DISCUSSING THE ATTEMPT TO LEGALIZE |
| EXISTING WORK THROUGH ASSURING THE RECONFIGURATION OF |
| THE SPACE COMPLIES WITH THE AFOREMENTIONED FBC 2017 |
| EXISTING BUILDING CHAPTER 10 CHANGE OF OCCUPANCY. PRIOR |
| TO PERMIT ISSUANCE THE APPROVED PLAN WILL NEED TO BE |
| REVIEWED BY THE PBC IMPACT FEE OFFICE AND A FEE MAY BE |
| DUE TO THEM. AN APPROPRIATE VALE FOR THIS WORK WILL |
| NEED TO BE ESTABLISHED. $1,200.00 SEEMS LOW. IF ANY NEW |
| WORK IS TO BE DONE, SEPARATE PERMITS PER TRADE WILL BE |
| REQUIRED. |
| |
| THE SUBMITTED PLAN IS DEFICIENT AND DOES NOT MEET THE |
| MINIMUM PLAN REVIEW CRITERIA REQUIRED IN FBC 107 AND |
| THE ITEMS LISTED GENERALLY ABOVE. A COMPLETE REIVEW |
| CANNOT BE CONDUCTED. PLEASE NOTE THAT ANY REVIEWS |
| COMPLETED PRIOR TO THIS DATE AND APPROVED ARE SUBJECT |
| TO CHANGE. |
| |
| |
| STEVEN KENNEDY, CBO |
| ASSISTANT BUILDING OFFICIAL |
| (561) 805-6710 |
| [email protected] |
| |