2018-04-10 11:26:151ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A CODE COMPLIANT SANITARY ISOMETRIC DRAWING.
 PER WPB AMEND TO FBC 107.3.5.1.3
  
 2. PROVIDE DIMENSIONS FOR BATHROOMS TO SHOW COMPLIANCE
 WITH FBC PL 405.3.1
  
 3. PLACE NOTE ON PLAN PIPES MAY NEED TO BE EXPOSED FOR
 INSPECTION UP TO THE DISCRETION OF THE FIELD INSPECTOR.
 PER FBC PL 312
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  