2018-04-23 11:03:29 | PERMIT # 18030117 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAILED COMMENTS: | | | | 1) PER NFPA 101, CHAPTER 30 - NEW APARTMENTS | | 30.3.5.1: ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT | | BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM. | | | | 2) HARD-WIRED MULTI-STATION SMOKE ALARMS SHALL BE | | INSTALLED ON ALL LEVELS OF THE DWELLING UNIT, INSIDE | | EACH BEDROOM AND DIRECTLY OUTSIDE BEDROOM DOORS. | | | | 3) PLEASE REVIEW AND COMPLY WITH ALL OTHER PLAN REVIEW | | COMMENTS. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|