Notes
Date Text
2018-03-03 09:31:22DENIED
  
 1. YOUR DEVICE DOES NOT MEET THE CROSS CONNECTION
 STANDARDS SET BY WPB PLEASE PROVIDE DOCUMENTATION THAT
 THE PROPOSED BACKFLOW DEVICE IS ON THE APPROVED DEVICE
 LIST PUBLISHED BY THE UNIVERSITY OF SOUTHERN CALIFORNIA
 (USC).
  
 2. ALL BACKFLOW DEVICES MUST BE LEAD-FREE. LEAD-FREE
 (LF) SHALL BE INCLUDED IN THE SERIAL NUMBER OR STAMPED
 ON THE BODY OF THE DEVICE. ANY DEVICE THAT HAS BEEN
 ALTERED AFTER BEING ASSEMBLED BY THE MANUFACTURER WILL
 NOT BE APPROVED. I HAVE GONE TO AMES WEBSITE TO
 RESEARCH IT AND THIS DEVICE IS STAINLESS STEEL. ON YOUR
 SUBMITTAL SHEET IT DOES REFER TO IT BEING LEAD-FREE BUT
 THAT IS THE BODY ONLY. THE VALVE AT EACH END MAY HAVE
 LEAD CONTENT AND THIS IS WHY THE UNIVERSITY OF SOUTHERN
 CALIFONIA HAS NOT APPROVED IT.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW