Plan Review Notes For Permit 18030102 |
Permit Number |
18030102 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-04-20 07:16:35 | 04/20/2018 2ND PLUMBING REVIEW**DEINED** | | | | 1) LAV SINK ON 1ST FLOOR SHOWING ON SANITARY RISER | | ISOMETRIC SHALL NOT CONNECT INTO THE STACK THAT | | RECEIVESDISCHARGE FROM A TOILET. FBC-R P 3109.2 LAV | | SINK DOES NOT SHOW ON FLOOR PLAN. | | | | 2) 2ND FLOOR GUEST BATHRROM ONLY 1 WET VENTED FIXTURE | | IS PERMITTED BEYOND THE VENT. FBC-R P3108.2.1 | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|