2018-04-20 07:16:3504/20/2018 2ND PLUMBING REVIEW**DEINED**
  
 1) LAV SINK ON 1ST FLOOR SHOWING ON SANITARY RISER
 ISOMETRIC SHALL NOT CONNECT INTO THE STACK THAT
 RECEIVESDISCHARGE FROM A TOILET. FBC-R P 3109.2 LAV
 SINK DOES NOT SHOW ON FLOOR PLAN.
  
 2) 2ND FLOOR GUEST BATHRROM ONLY 1 WET VENTED FIXTURE
 IS PERMITTED BEYOND THE VENT. FBC-R P3108.2.1
  
  