Plan Review Notes
Plan Review Notes For Permit 18030102
Permit Number 18030102
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-22 17:52:1703/22/2018 1ST REVIEW**DENIED**
  
 ON P-3 RISER DIAGRAM, 1 ST FLOOR BATHROOM GROUP CANNOT
 RUN ON THE MAIN TRUNK LINE, SHOW IT AS A BRANCH AND OR
 A AVV, REVENT OR VENT IT OUTSIDE THE UNIT AND DO THE
 SAME FOR THE SECOND FLOOR. FBC R 3104.6 VENT FOR FUTURE
 FIXTURES.
  
 ROMAN TUB REQUIRES A THERMOSTATIC VALVE IN AN
 ACCESSIBLE LOCATION IF SHALL COMPLY WITH ASSE 1017 FBC
 R 2724.1 TEMPERATURE-ACTUATED MIXING VALVES.
  
 PLEASE SHOW WHERE A THERMAL EXPANSION DEVICE IS LOCATED
 FBC R2903.4 THERMAL EXPANSION CONTROL.
  
 THE PLAN SHOWS A POOL AND A SEPARATE BACKFLOW
 PREVENTION DEVICE MAY BE REQUIRED DEPENDING ON FACTORS
 LIKE A POOL FILL AND INSTALLED BY A LICENSED CONTRACTOR
 WITH A SEPARATE APPLICATION AND INSPECTION. FBC R
 2902.3 BACKFLOW PROTECTION.
 REFER TO THE ITEM BELOW FOR COMPLIANCE
 A. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE
 PROPOSED BACKFLOW PREVENTION DEVICE.
 B. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR
 THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF
 THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK
 SECTION ON THE PERMIT APPLICATION.
 C. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE.
 D. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS
 ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY
 OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT
 OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT
 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE
 PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY
 REQUIREMENTS.
 E. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST
 PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A
 LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES
 PRIOR TO FINAL INSPECTION. PLEASE CONTACT CITY OF WPB
 UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS.
  
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FORM A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE
 ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. A
 SEPARATE GAS PERMIT REQUIRED AND A GAS RISER DIAGRAM
 REQUIRED. A NOTE CAN THAT PUT ON PLANS THAT SUBMITTAL
 FOR PRODUCT APPROVAL WILL BE SUBMITTED FOR APPLIANCES
 AND ALL GAS RELATED DOCUMENT. WPB AMENDMENTS TO THE FBC
 SEC. 107.3.5.3 (12) RESIDENTIAL GAS
 REFER TO THE ITEM BELOW FOR COMPLIANCE
 A. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2.
 B. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 C. TYPE OF GAS, (LP OR NATURAL).
 D. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2017 FBC FUEL GAS RES.
 SEC. G2413.
 E. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR STOVE PER
 THE FBC-2017 FUEL GAS CODE SEC. 304.
 F. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2017 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & INDICATE THE
 DELIVERY PRESSURE (PSI) PER FBC-2017 FUEL GAS SEC.
 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2017 FUEL GAS SEC. 402.2
  
 ALL PLUMBING MUST COMPLY WITH FLORIDA BUILDING CODE
 2017 6TH EDITION.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved