Date |
Text |
2018-03-22 17:52:17 | 03/22/2018 1ST REVIEW**DENIED** |
| |
| ON P-3 RISER DIAGRAM, 1 ST FLOOR BATHROOM GROUP CANNOT |
| RUN ON THE MAIN TRUNK LINE, SHOW IT AS A BRANCH AND OR |
| A AVV, REVENT OR VENT IT OUTSIDE THE UNIT AND DO THE |
| SAME FOR THE SECOND FLOOR. FBC R 3104.6 VENT FOR FUTURE |
| FIXTURES. |
| |
| ROMAN TUB REQUIRES A THERMOSTATIC VALVE IN AN |
| ACCESSIBLE LOCATION IF SHALL COMPLY WITH ASSE 1017 FBC |
| R 2724.1 TEMPERATURE-ACTUATED MIXING VALVES. |
| |
| PLEASE SHOW WHERE A THERMAL EXPANSION DEVICE IS LOCATED |
| FBC R2903.4 THERMAL EXPANSION CONTROL. |
| |
| THE PLAN SHOWS A POOL AND A SEPARATE BACKFLOW |
| PREVENTION DEVICE MAY BE REQUIRED DEPENDING ON FACTORS |
| LIKE A POOL FILL AND INSTALLED BY A LICENSED CONTRACTOR |
| WITH A SEPARATE APPLICATION AND INSPECTION. FBC R |
| 2902.3 BACKFLOW PROTECTION. |
| REFER TO THE ITEM BELOW FOR COMPLIANCE |
| A. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE |
| PROPOSED BACKFLOW PREVENTION DEVICE. |
| B. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR |
| THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF |
| THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK |
| SECTION ON THE PERMIT APPLICATION. |
| C. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE. |
| D. DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE IS |
| ON THE APPROVED DEVICE LIST PUBLISHED BY THE UNIVERSITY |
| OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT DEPARTMENT |
| OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT |
| 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE |
| PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY |
| REQUIREMENTS. |
| E. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| PRIOR TO FINAL INSPECTION. PLEASE CONTACT CITY OF WPB |
| UTILITIES AT 561-822-2240 FOR FURTHER DIRECTIONS. |
| |
| A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL |
| PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT |
| THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE |
| REQUIRED FORM A CONTRACTOR TO PERFORM THE RELATED WORK. |
| PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE |
| ENTIRE SCOPE OF GAS WORK TO BE DONE. AT THIS TIME. A |
| SEPARATE GAS PERMIT REQUIRED AND A GAS RISER DIAGRAM |
| REQUIRED. A NOTE CAN THAT PUT ON PLANS THAT SUBMITTAL |
| FOR PRODUCT APPROVAL WILL BE SUBMITTED FOR APPLIANCES |
| AND ALL GAS RELATED DOCUMENT. WPB AMENDMENTS TO THE FBC |
| SEC. 107.3.5.3 (12) RESIDENTIAL GAS |
| REFER TO THE ITEM BELOW FOR COMPLIANCE |
| A. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL |
| CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER |
| FBC-2017 FUEL GAS, SECS. 402.4.1, 402.4.2. |
| B. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS |
| STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB |
| AMENDMENTS TO FBC SEC. 107.2.1. |
| C. TYPE OF GAS, (LP OR NATURAL). |
| D. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON |
| THE SYSTEM. REFER TO THE FBC-2017 FBC FUEL GAS RES. |
| SEC. G2413. |
| E. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR STOVE PER |
| THE FBC-2017 FUEL GAS CODE SEC. 304. |
| F. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND/OR SYSTEM PER THE FBC-2017 FUEL GAS APPENDIX A ? |
| USE OF CAPACITY SECTION A.3.1(4) & INDICATE THE |
| DELIVERY PRESSURE (PSI) PER FBC-2017 FUEL GAS SEC. |
| 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| G. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC-2017 FUEL GAS SEC. 402.2 |
| |
| ALL PLUMBING MUST COMPLY WITH FLORIDA BUILDING CODE |
| 2017 6TH EDITION. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| [email protected] |
| 561-805-6720 |
| |