2018-03-12 15:26:29 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLAN SHOWS A CARBON MONOXIDE ALARM ON SECOND FLOOR |
| IN HALLWAY. IN ADDITION TO THE CO ALARM, A SMOKE ALARM |
| IS REQUIRED IN THIS LOCATION. ADDITIONALLY, THE |
| DOWNSTAIRS BEDROOM SHOULD HAVE A SMOKE ALARM INSIDE THE |
| BEDROOM AS WELL AS A SMOKE/CO ALARM WITHIN 10 FEET OF |
| THE BEDROOM, PROVIDE CORRECTION. FBC RE R314.3, R315.1 |
| 2. PLAN SHOWS A MAIN DISCONNECT ON THE OUTSIDE OF A |
| HOME, FEEDING AN INTERIOR PANEL. THE CONDUCTORS TO |
| INTERIOR PANEL SHOULD INCLUDE AN EQUIPMENT GROUNDING |
| CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE |
| E3704.6, 3607.3.1 |
| 3. PLAN SHOWS A STANDARD RECESS LIGHT OVER MASTER TUB. |
| LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE |
| FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D); |
| FBC RE E4003.11 |
| 4. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS. SECOND A/C SYSTEM IS NOT INCLUDED. DEMAND |
| FACTORS ARE NOT APPLIED PROPERLY. SUB-PANEL LOAD IS |
| SHOWN AS 12.0 KW IN MAIN PANEL, BUT AS 4.5 KW IN |
| SUB-PANEL. CLARIFY AND/OR CORRECT. SEE FBC RE FOR |
| FORMAT. NEC 220; FBC RE E3602.2 |
| 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND DATA |
| SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS |
| PRESENT. FBC 105.1, 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| SINCERELY, |
| |