2018-03-12 15:26:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN SHOWS A CARBON MONOXIDE ALARM ON SECOND FLOOR
 IN HALLWAY. IN ADDITION TO THE CO ALARM, A SMOKE ALARM
 IS REQUIRED IN THIS LOCATION. ADDITIONALLY, THE
 DOWNSTAIRS BEDROOM SHOULD HAVE A SMOKE ALARM INSIDE THE
 BEDROOM AS WELL AS A SMOKE/CO ALARM WITHIN 10 FEET OF
 THE BEDROOM, PROVIDE CORRECTION. FBC RE R314.3, R315.1
 2. PLAN SHOWS A MAIN DISCONNECT ON THE OUTSIDE OF A
 HOME, FEEDING AN INTERIOR PANEL. THE CONDUCTORS TO
 INTERIOR PANEL SHOULD INCLUDE AN EQUIPMENT GROUNDING
 CONDUCTOR. PROVIDE CORRECTION. NEC 250.122; FBC RE
 E3704.6, 3607.3.1
 3. PLAN SHOWS A STANDARD RECESS LIGHT OVER MASTER TUB.
 LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE
 FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D);
 FBC RE E4003.11
 4. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. SECOND A/C SYSTEM IS NOT INCLUDED. DEMAND
 FACTORS ARE NOT APPLIED PROPERLY. SUB-PANEL LOAD IS
 SHOWN AS 12.0 KW IN MAIN PANEL, BUT AS 4.5 KW IN
 SUB-PANEL. CLARIFY AND/OR CORRECT. SEE FBC RE FOR
 FORMAT. NEC 220; FBC RE E3602.2
 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 7. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  