2018-03-17 09:47:00 | 1ST REVIEW: FBC 2017 6TH EDITION |
| PLUMBING COMMENTS: |
| |
| 1. ALL WORK SHALL COMPLY WITH CURRENT CODE 2017 FBC |
| PLUMBING , FUEL GAS, ACCESSIBILITY |
| |
| 2. THERE IS NO PERMIT RECORD OF THREE COMPARTMENT SINK |
| OR CAN WASH THEY SHALL BE REVIEWED AS NEW WORK AND |
| SHALL COMPLY WITH CURRENT CODE. PER WPB AMEND TO FBC |
| 105.1 AND 107.2.1 |
| |
| 3. PLEASE PROVIDE SANITARY AND WATER ISOMETRIC |
| DRAWINGS. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| |
| 4. THE CAN WASH SHALL DISCHARGE TO A GREASE INTERCEPTOR |
| ALONG WITH THE 3 COMPARTMENT SINK. FBC PL 1003.3.1 |
| |
| 5. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE |
| INTERCEPTOR PLACE NOTE OM PLAN. PER WPB AMEND TO FBC |
| 105.1 AND 107.2.1 |
| |
| 6. THE CAN WASH SHALL BE COVERED TO PREVENT STORM WATER |
| FROM DISCHARGING TO SANITARY SYSTEM. PER WPB CODE OF |
| ORDINANCES SEC. 90-126.(5) |
| |
| 7. SHALL COMPLY WITH BUILDINGS COMMENTS |
| |
| 8. PROVIDE DETAIL FOR GREASE INTERCEPTOR, SIZING |
| CALCULATIONS AND MANUFACTURE SPECIFICATIONS AND |
| INSTILLATION GUIDE. PER WPB AMEND TO FBC 105.1 AND |
| 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |