Plan Review Notes
Plan Review Notes For Permit 18030077
Permit Number 18030077
Review Stop P
Sequence Number 1
Notes
Date Text
2018-03-17 09:47:001ST REVIEW: FBC 2017 6TH EDITION
 PLUMBING COMMENTS:
  
 1. ALL WORK SHALL COMPLY WITH CURRENT CODE 2017 FBC
 PLUMBING , FUEL GAS, ACCESSIBILITY
  
 2. THERE IS NO PERMIT RECORD OF THREE COMPARTMENT SINK
 OR CAN WASH THEY SHALL BE REVIEWED AS NEW WORK AND
 SHALL COMPLY WITH CURRENT CODE. PER WPB AMEND TO FBC
 105.1 AND 107.2.1
  
 3. PLEASE PROVIDE SANITARY AND WATER ISOMETRIC
 DRAWINGS. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 4. THE CAN WASH SHALL DISCHARGE TO A GREASE INTERCEPTOR
 ALONG WITH THE 3 COMPARTMENT SINK. FBC PL 1003.3.1
  
 5. A SEPARATE PERMIT IS REQUIRED FOR THE GREASE
 INTERCEPTOR PLACE NOTE OM PLAN. PER WPB AMEND TO FBC
 105.1 AND 107.2.1
  
 6. THE CAN WASH SHALL BE COVERED TO PREVENT STORM WATER
 FROM DISCHARGING TO SANITARY SYSTEM. PER WPB CODE OF
 ORDINANCES SEC. 90-126.(5)
  
 7. SHALL COMPLY WITH BUILDINGS COMMENTS
  
 8. PROVIDE DETAIL FOR GREASE INTERCEPTOR, SIZING
 CALCULATIONS AND MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDE. PER WPB AMEND TO FBC 105.1 AND
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  