2018-03-16 11:00:20 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. THE NEC AND FBC SPECIFIED FOR DESIGN IS NOT THE |
| CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE (ALSO SEE |
| CURRENT CODES ABOVE) |
| 2. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE, |
| INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF |
| SERVICE IS ADEQUATE. CURRENT CALCULATION USES THE |
| SMALLER OF THE AC EQUIPMENT LOAD AND SHOULD USE THE |
| LARGER OF THE TWO. ADDITIONALLY, SERVICE SHOULD BE |
| SIZED FOR 125% OF CONTINUOUS LOADS PLUS 100% OF THE |
| NON-CONTINUOUS LOADS. PROVIDE CORRECTIONS. NEC 215.2, |
| 220, 220.60, 408.30 |
| 3. BASED ON COMMENT NUMBER 2, IT APPEARS THAT THE |
| CURRENT SERVICE IS NOT ADEQUATE FOR THE ADDITIONAL |
| LOAD. PROVIDE CORRECT SIZE SERVICE FOR LOAD IF |
| CALCULATION DEMANDS. NEC 230.79 |
| 4. IF SERVICE IS TO BE REPLACED, PROVIDE AVAILABLE |
| SHORT CIRCUIT CALCULATION FOR EACH PANEL INCLUDING |
| INFORMATION FROM THE POWER COMPANY STATING WHAT THE |
| AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO |
| CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT |
| AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10 |
| 5. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| CODE. NEC 210.64 |
| 6. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| EQUIPMENT PER CODE. NEC 210.63 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |