2018-03-16 08:17:352017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18030077
 ADD: 4106 BROADWAY SUITE: 4104
 CONT: ACTION MECHANICAL CONTRACTORS INC.
 TEL: 561-642-4730
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 15/ 2018
 ACTION: DENIED
  
 1)SHEET A1. PLEASE UPDATE THE CODE FROM THE 2014 FBC TO
 THE 2017 FBC. PLEASE NOTE ON DEC. 31 / 2017 THE 2017
 FLORIDA BUILDING CODE WERE ADOPTED STATEWIDE.
  
 2) SHEET A1. PLEASE CORRECT THE OCCUPANCY TYPE THIS IS
 NOT A A2 OCCUPANCY, THERE WOULD NEED TO BE A MINIMUM OF
 50 OCCUPANTS IN A RESTAURANT. THE TENANT SPACE IS A
 CHANGE IN USE BUT STILL A MERCANTILE OCCUPANCY. FBC-B
 309.1 MERCANTILE GROUP M OCCUPANCY INCLUDES, AMONG
 OTHERS, THE USE OF A BUILDING OR STRUCTURE OR A PORTION
 THEREOF FOR THE DISPLAY AND SALE OF MERCHANDISE, AND
 INVOLVES STOCKS OF GOODS, WARES OR MERCHANDISE
 INCIDENTAL TO SUCH PURPOSES AND ACCESSIBLE TO THE
 PUBLIC.
  
 3) THE WORK INVOLVED IN THIS CHANGE IN USE WILL REQUIRE
 A BUILDING PERMIT AS WELL AS THE MECHANICAL PERMIT.
 EITHER A BUILDING CONTRACTOR OR GENERAL CONTRACTOR WILL
 BE REQUIRED TO SIGN ONTO A BUILDING PERMIT. F. S.
 489.105 DEFINITIONS, GENERAL CONTRACTOR OR BUILDING
 CONTRACTOR. F. S. 489.113 QUALIFICATIONS FOR PRACTICE;
 RESTRICTIONS.
  
 4) PLEASE NOTE THE WORK BEING COMPLETED UNDER THIS
 PERMIT AND PERMIT 17030415 (GAS) IS CREATING A CHANGE
 IN USE, A COMMERCIAL KITCHEN AND WILL NEED TO SHOW
 COMPLIANCE WITH THE:
  
 2017 FLORIDA EXISTING BUILDING CODE SECTION 1001.2.1
 CHANGE OF USE. ANY WORK UNDERTAKEN IN CONNECTION WITH A
 CHANGE IN USE THAT DOES NOT INVOLVE A CHANGE OF
 OCCUPANCY CLASSIFICATION OR A CHANGE TO ANOTHER GROUP
 WITHIN AN OCCUPANCY CLASSIFICATION SHALL CONFORM TO THE
 APPLICABLE REQUIREMENTS FOR THE WORK AS CLASSIFIED IN
 CHAPTER 5 AND TO THE REQUIREMENTS OF SECTIONS 1002
 THROUGH 1011.
  
 1010.1 EXIST. BLDG CODE. 1010.1. WHERE THE OCCUPANCY OF
 AN EXISTING BUILDING OR PART OF AN EXISTING BUILDING IS
 CHANGED SUCH THAT THE NEW OCCUPANCY IS SUBJECT TO
 DIFFERENT PLUMBING FIXTURE REQUIREMENTS IN ACCORDANCE
 WITH THE FLORIDA BUILDING CODE, PLUMBING, THE NEW
 OCCUPANCY SHALL COMPLY WITH THE INTENT OF THE
 RESPECTIVE FLORIDA BUILDING CODE, PLUMBING PROVISIONS.
  
 2017 FBC-B 2902.3.6 PROHIBITED TOILET ROOM LOCATION.
 TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A ROOM USED
 FOR THE PREPARATION OF FOOD FOR SERVICE TO THE PUBLIC.
  
 5) THE 2ND PROBLEM WITH THE LOCATION WITH THE EXISTING
 LOCATION OF THE RESTROOM IN A COMMERCIAL KITCHEN IS THE
 OCCUPANTS CANNOT GO THROUGH THE KITCHEN TO GAIN ENTRY
 OF THE RESTROOM. 2017 FBC-B 1016.2 EGRESS THROUGH
 INTERVENING SPACES. EGRESS THROUGH INTERVENING SPACES
 SHALL COMPLY WITH THIS SECTION. (5.) EGRESS SHALL NOT
 PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR SPACES
 USED FOR SIMILAR PURPOSES.
  
 6) SHEET M2 SHOWS A NEW ROOF TOP 3 TON A/C UNIT AND A
 NEW ROOF EXHAUST FAN. THE ARCHITECTURAL SHEET NOR THE
 MECHANICAL SHEETS SHOW THE TYPE OF ROOF FRAMING SYSTEM
 IS WITHIN THIS TENANT SPACE NOR HOW THE PENETRATION
 THROUGH THE ROOF DECK WILL BE MADE NOR THE REQUIRED
 EXTRA FRAMING AROUND THE NEW PENETRATION, IF EXTRA
 FRAMING MEMBERS WILL BE REQUIRED, NOR THE TYPE OF ROOF
 CURB, AND THE ANCHORING OF THE ROOF CURB TO THE ROOF
 FRAMING MEMBERS.
  
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 7) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THE ROOF
 TOP UNIT.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 7.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 7.2. RISK CATEGORY.
  
 7.HEIGHT AND EXPOSURE.
  
 7.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 7.DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 8) 2014 / 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS
 OR VENTILATORS (NOT REVIEWED BY THE DESIGNER OF RECORD,
 SHOP DRAWING STAMP OF APPROVAL).
  
 9) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) PLEASE BE AWARE WITH THE MOVING OF THE RESTROOM
 FROM BEING IN THE KITCHEN PLEASE KEEP IN MIND THE NEW
 RESTROOM WILL NEED TO MEET ALL OF THE RESTROOM
 REQUIREMENTS OF THE 2017 FBC-ACCESSIBILITY CODE IN
 CHAPTER 6.
  
 11) PLEASE ALSO BE AWARE THAT YOU WILL NEED TO DECLARE
 COMPLIANCE WITH DISPROPORTIONATE COST OF THE:
  
 2017 ACCESSIBILITY CODE. 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved