2018-04-04 14:29:1704/04/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS NOTE
  
 A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) SECOND NOTICE, THE PRINTED INFORMATION ON THE SURVEY
 FOR THE GAS IS SO SMALL IT CAN BARELY BE READ. SUBMIT
 THE SURVEY WITH NOTES THAT CAN BE READ. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) SECOND NOTICE, THE SIZING TABLE COPIES FOR THE
 SCHEDULE 40 METALLIC PIPE AND PE PIPE ARE BARELY
 LEGIBLE. SUBMIT TWO CLEAR AND LEGIBLE COPIES OF THESE
 SIZING TABLES. WPB AMEND. TO FBC SEC. 107.2.1.
 3) SECOND NOTICE, THE SIZING TABLE YOU SUBMITTED FOR
 THE SCHEDULE 40 METALLIC PIPE HAS A MINIMUM LENGTH OF
 10 FEET FOR A SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR
 A 3/4 INCH LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE
 SHOWING THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM
 SIZE PIPE ON THE LOW PRESSURE SIDE TO THE GENERATOR
 SHALL BE 1 INCH.
 4) SECOND NOTICE, SUBMIT PAGES 40 & 41 OF THE
 MANUFACTURES SPECS FOR THE REGULATORS. THESE SHEETS
 DETAIL THE INSTALLATION METHOD FOR THE REGULATORS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) SECOND NOTICE, THERE IS AN EXPIRED GAS PERMIT ON
 THIS PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594
 ) THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A
 FINAL GAS INSPECTION. PLEASE DISCUSS THIS WITH THE
 CURRENT OWNER OF THE PROPERTY AND I CAN BE CONTACTED
 WITH ANY QUESTIONS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  
  
  
  
  