Plan Review Notes For Permit 18030063 |
Permit Number |
18030063 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-14 06:26:19 | 1) THE PRINTED INFORMATION ON THE SURVEY FOR THE GAS IS | | SO SMALL IT CAN BARELY BE READ. SUBMIT THE SURVEY WITH | | NOTES THAT CAN BE READ. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) THE SIZING TABLE COPIES FOR THE SCHEDULE 40 METALLIC | | PIPE AND PE PIPE ARE BARELY LEGIBLE. SUBMIT TWO CLEAR | | AND LEGIBLE COPIES OF THESE SIZING TABLES. WPB AMEND. | | TO FBC SEC. 107.2.1. | | 3) THE SIZING TABLE YOU SUBMITTED FOR THE SCHEDULE 40 | | METALLIC PIPE HAS A MINIMUM LENGTH OF 10 FEET FOR A | | SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR A 3/4 INCH | | LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE SHOWING | | THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM SIZE PIPE | | ON THE LOW PREESSURE SIDE TO THE GENERATOR SHALL BE 1 | | INCH. | | 4) SUBMIT PAGES 40 & 41 OF THE MANUF. SPECS FOR THE | | REGULATORS. THESE SHEETS DETAIL THE INSTALLATION METHOD | | FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1. | | 5) NOTE: THERE IS AN EXPIRED GAS PERMIT ON THIS | | PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594 ) | | THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A FINAL | | GAS INSPECTION. PLEASE DISCUSS THIS WITH THE CURRENT | | OWNER OF THE PROPERTY AND I CAN BE CONTACTED WITH ANY | | QUESTIONS. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|