2018-03-14 06:26:191) THE PRINTED INFORMATION ON THE SURVEY FOR THE GAS IS
 SO SMALL IT CAN BARELY BE READ. SUBMIT THE SURVEY WITH
 NOTES THAT CAN BE READ. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE SIZING TABLE COPIES FOR THE SCHEDULE 40 METALLIC
 PIPE AND PE PIPE ARE BARELY LEGIBLE. SUBMIT TWO CLEAR
 AND LEGIBLE COPIES OF THESE SIZING TABLES. WPB AMEND.
 TO FBC SEC. 107.2.1.
 3) THE SIZING TABLE YOU SUBMITTED FOR THE SCHEDULE 40
 METALLIC PIPE HAS A MINIMUM LENGTH OF 10 FEET FOR A
 SIZING DISTANCE. THE MAXIMUM BTU LOAD FOR A 3/4 INCH
 LINE AT 10 FEET IS 360,000 BTU'S AND YOU ARE SHOWING
 THE GENERATOR AS 480,000 BTU'S SO THE MINIMUM SIZE PIPE
 ON THE LOW PREESSURE SIDE TO THE GENERATOR SHALL BE 1
 INCH.
 4) SUBMIT PAGES 40 & 41 OF THE MANUF. SPECS FOR THE
 REGULATORS. THESE SHEETS DETAIL THE INSTALLATION METHOD
 FOR THE REGULATORS. WPB AMEND. TO FBC SEC. 107.2.1.
 5) NOTE: THERE IS AN EXPIRED GAS PERMIT ON THIS
 PROPERTY FROM 2007 ( PERMIT APPLICATION # 07060594 )
 THIS PERMIT WILL HAVE TO BE RENEWED AND RECEIVE A FINAL
 GAS INSPECTION. PLEASE DISCUSS THIS WITH THE CURRENT
 OWNER OF THE PROPERTY AND I CAN BE CONTACTED WITH ANY
 QUESTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  