Plan Review Notes
Plan Review Notes For Permit 18030045
Permit Number 18030045
Review Stop B
Sequence Number 2
Notes
Date Text
2018-08-14 13:11:05SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE PREVIOUS LIST. THE OLD SUBMITTAL IS IN THE
 PACKAGE, AS WELL AS THREE SETS OF NEW PRODUCT
 APPROVALS. NEW PRODUCT APPROVALS APPEAR TO BE FOR SOME
 DOORS, BUT IT APPEARS THAT SOME ARE INCLUDED IN THE
 PREVIOUS SUBMITTAL.
  
 FOR INSTANCE: NOA FOR DOOR P123B IS IN THE OLD
 SUBMITTAL AND IS STAMPED (APPROVED). IT IS NOT LISTED
 IN THE REVISED CHART OF OPENINGS.
  
 PROVIDE THREE COLLATED SETS OF PERMIT DOCUMENTS FOR
 ISSUANCE. MARK OLD SHEETS "VOID".
  
 2. A PORTION OF A PRODUCT APPROVAL WAS SUBMITTED
 (FL16353.2); THE COMPLETE APPROVAL IS IN THE OLD
 PACKAGE BUT IS LABELED THAT IT IS FOR ONE DOOR, BUT
 APPEARS IT WILL BE USED FOR MULTIPLE DOORS.
  
 3. FL16353.2 HAS OPTIONS CIRCLED WHICH INCLUDE WATER
 INTRUSION AND WHERE WATER INTRUSION IS NOT NEEDED (P.
 2, ASSEMBLY 3 AND ASSEMBLY 4). IT IS NOT CLEAR IF WATER
 INTRUSION IS ALLOWED; INDICATE WHICH OPTION IS
 PROPOSED.
  
  
  