Plan Review Notes For Permit 18030045 |
Permit Number |
18030045 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-08-14 13:11:05 | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEE PREVIOUS LIST. THE OLD SUBMITTAL IS IN THE | | PACKAGE, AS WELL AS THREE SETS OF NEW PRODUCT | | APPROVALS. NEW PRODUCT APPROVALS APPEAR TO BE FOR SOME | | DOORS, BUT IT APPEARS THAT SOME ARE INCLUDED IN THE | | PREVIOUS SUBMITTAL. | | | | FOR INSTANCE: NOA FOR DOOR P123B IS IN THE OLD | | SUBMITTAL AND IS STAMPED (APPROVED). IT IS NOT LISTED | | IN THE REVISED CHART OF OPENINGS. | | | | PROVIDE THREE COLLATED SETS OF PERMIT DOCUMENTS FOR | | ISSUANCE. MARK OLD SHEETS "VOID". | | | | 2. A PORTION OF A PRODUCT APPROVAL WAS SUBMITTED | | (FL16353.2); THE COMPLETE APPROVAL IS IN THE OLD | | PACKAGE BUT IS LABELED THAT IT IS FOR ONE DOOR, BUT | | APPEARS IT WILL BE USED FOR MULTIPLE DOORS. | | | | 3. FL16353.2 HAS OPTIONS CIRCLED WHICH INCLUDE WATER | | INTRUSION AND WHERE WATER INTRUSION IS NOT NEEDED (P. | | 2, ASSEMBLY 3 AND ASSEMBLY 4). IT IS NOT CLEAR IF WATER | | INTRUSION IS ALLOWED; INDICATE WHICH OPTION IS | | PROPOSED. | | | | | | |
|