2018-03-07 11:50:27 | 2010 FBC- BUILDING PLAN REVIEW |
| W. P. B. SUBMITTAL: 18030045 |
| W. P. B. PERMIT: 15111020 |
| ADD: 1100 S. FLAGLER DR. |
| CONT: SUFFOLK |
| TEL: 786-412-3287 |
| E-MAIL: [email protected] |
| |
| 2010 FLORIDA BUILDING CODE W 2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 1ST REVIEW |
| DATE: WED. MARCH 07/2018 |
| ACTION: DENIED |
| |
| 1) THE DOOR SUBMITTAL HAD NO PLANS ASSOCIATED WITH THE |
| PRODUCT APPROVALS. PRESSURES WERE TAKEN FROM THE WIND |
| TUNNEL TESTING BY CPP/ CERMAK, PETERKA & PETERSON. WALL |
| PRESSURES ARE SHOWN ON SHEETS 18-21 WITH SHEET 22 THE |
| PEAK CLADDING PRESSURES FOR LEVEL 26 THE MECHANICAL |
| EQUIPMENT ROOM LEVEL. |
| |
| PRESSURES SHOWN ON THE WIND TUNNEL TESTING REPORT ARE |
| IN VASD, HAD TO CONVERT PRESSURES TO VASD. THE DOORS |
| LISTED UNDER THE FL 16355.2 R-1 DOOR TAG NUMBER |
| 2602,2603A, 2603B, 2604A, 2604B , P138, ST01-01A & |
| ST04-01A THE PRESSURES WERE LOW FOR THE PRODUCT |
| APPROVAL. PAGE 3 OF THE PRODUCT APPROVAL INDICATE THE |
| DOORS ARE ONLY GOOD FOR +70/-70 PSF VASD. |
| THE PRESSURES INDICATED FOR LEVEL 26 MECH. ARE ALL -87/ |
| +54. NEGATIVE PRESSURES HIGH THAN THE PRODUCT APPROVAL. |
| DOOR P01F GARAGE EXTERIOR ACCESS -108/ +54 PSF VASD.. |
| DOOR 138 WATER FEATURE VAULT -108/ +54 PSF. VASD. |
| ST01-01A STAIR # 1 -108/+69 PSF, VASD. |
| ST04-01A STAIR # 4 -60/ +75 PSF, VASD. |
| |