Plan Review Notes For Permit 18030040 |
Permit Number |
18030040 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-03-22 10:46:47 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18030040 | | 3/22/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE A VENTILATION CALCULATION FOR THE STORAGE | | BUILDING IN COMPLIANCE WITH TABLE 403.1.1. | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXHAUST FAN. | | | | 3) PROVIDE OPENING PROTECTION AT THE FAN LOCATION IN | | THE EXTERIOR WALL IN ACCORDANCE WITH RULE 9N-3 FAC. | | TYPICALLY AN IMPACT RATED LOUVER THAT HAS EITHER | | MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL WOULD BE | | INSTALLED. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|