Plan Review Notes
Plan Review Notes For Permit 18030040
Permit Number 18030040
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-07 11:55:48THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS NO INDICATION OF EXIT SIGNAGE.
  
 PER NFPA 101, CHAPTER 42 STORAGE OCCUPANCIES
  
 42.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 CHAPTER 7, MEANS OF EGRESS
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
  
  
 PLEASE PROVIDE ON EITHER DOOR OR BOTH.
  
  
  
 2) THERE IS NO INDICATION OF EXIT ILLUMINATION
  
 42.2.8 ILLUMINATION OF MEANS OF EGRESS.
 42.2.8.1 MEANS OF EGRESS SHALL BE ILLUMINATED IN
 ACCORDANCE WITH
 SECTION 7.8.
 42.2.8.2 IN STRUCTURES OCCUPIED ONLY DURING DAYLIGHT
 HOURS, MEANS
 OF EGRESS SHALL BE PERMITTED TO BE ILLUMINATED WITH
 WINDOWS
 ARRANGED TO PROVIDE THE REQUIRED LEVEL OF ILLUMINATION
 ON ALL
 PORTIONS OF THE MEANS OF EGRESS DURING SUCH HOURS, WHEN
 APPROVED
 BY THE AUTHORITY HAVING JURISDICTION.
 42.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN NORMALLY OCCUPIED STORAGE OCCUPANCIES IN
 ACCORDANCE
 WITH SECTION 7.9, EXCEPT FOR SPACES OCCUPIED ONLY
 DURING DAYLIGHT
 HOURS WITH NATURAL ILLUMINATION IN ACCORDANCE WITH
 42.2.8.2.
  
 PLEASE PROVIDE PER THE REQUIREMENT.
  
  
 3) PROVIDE A LIGHT - FRAME ROOF TRUSS SIGN.
  
 PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR
 STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION.
 ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT
 RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES
 HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A
 MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND
 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR.
 THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO
 THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
 THE FIRE INSPECTOR WILL REVIEW AND VERIFY ON FIRE
 INSPECTIONS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  