2018-03-22 12:02:00 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | PLUMBING COMMENTS: APPROVED WITH PROVISO SHALL BE | | CORRECTED ON MASTER. | | | | 1. THE BATHROOMS 244 + 215 SHOW A TUB ON THE FLOOR PLAN | | AND A SHOWER ON THE ISOMETRIC DRAWING PLEASE CLARIFY. | | PER WPB AMEND TO FBC 107.2.1 | | | | 2. THE ISOMETRIC DOES NOT MATCH THE FLAT DRAWING AT THE | | BRANCH FOR THE POWDER ROOM 135. THE FLAT DRAWING SHOWS | | 1 BRANCH CONNECTING THE POWDER ROOM AND 2 SOIL STACKS | | THE ISOMETRIC DRAWING SHOWS 2 SEPARATE BRANCHES | | CONNECTING THE POWDER ROOM AND THE SOIL STACKS. PER WPB | | AMEND TO FBC 107.2.1 | | | | 3. PROVIDE DETAIL FOR DRY WELL FOR OUTSIDE SHOWER. PER | | WPB AMEND TO FBC 107.2.1.2 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|