Plan Review Notes
Plan Review Notes For Permit 18021224
Permit Number 18021224
Review Stop P
Sequence Number 2
Notes
Date Text
2018-06-01 15:42:091ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED
  
 7) SHT. A2.2 - THE STANDARD TOILET STALL IN THE WOMEN'S
 RESTROOM SHALL BE A MINIMUM OF 60 INCHES FOR FLOOR
 MOUNTED WATER CLOSETS. 2017 FBC-PLUMBING SEC.405.3.1.
  
 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 BREWERY TANKS. WPB AMEND. TO FBC SEC. 107.2.1.
  
 14) SUBMIT A PIPING DETAIL FOR ALL THE PROCESS PIPING
 FOR ALL THE TANKS INVOLVED IN THE BREWING PROCESS AND
 THE KEG WASHER. WPB AMEND. TO FBC SEC. 107.2.1.
  
 21) SUBMIT DOCUMENTATION FOR THE TYPE OF WASTE THAT
 WILL BE DISCHARGED INTO THE TRENCH DRAIN AND ALSO FROM
 THE KEG WASHER. DEPENDING ON THE TYPE OF WASTE, AN
 INTERCEPTOR OR SEPARATOR MAY BE REQUIRED IN THE DRAIN
 LINE FROM THESE AREAS. 2017 FBC-PLUMBING SEC.1003.1.
  
 NEW COMMENTS:
  
 1. SHT. A2.2 DETAIL #7 IS SHOWING THE LAVATORY AT
 341/2" THE CODE IS 34" MAX PLEASE CLARIFY PER FBC ACC
 606.3
  
 2. SHT. A2.2 DETAIL #7 IS SHOWING THE SIDE GRAB BAR AT
 48" OF THE REAR WALL IT SHALL BE 54" MIN PER FBC ACC
 604.5.1
  
 3. SHT. A2.2 THE TOILET PAPER DISPENSER SHALL BE 7-9
 OFF THE FRONT OF THE TOILET PER FBC ACC 604.7
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 5. THE VENT FOR THE FLOOR SINK THE TRENCH DRAINS ARE
 DUMPING IS A HORIZONTAL DRY VENT WHICH IS PROHIBITED BY
 CODE IT SHALL COMPLY WITH FBC PL 905.3 , 905.4
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved