2018-06-01 15:42:09 | 1ST REVIEW: FBC 2017 6TH EDITION |
| |
| PLUMBING COMMENTS: PREVIOUS COMMENT NOT COMPLIED |
| |
| 7) SHT. A2.2 - THE STANDARD TOILET STALL IN THE WOMEN'S |
| RESTROOM SHALL BE A MINIMUM OF 60 INCHES FOR FLOOR |
| MOUNTED WATER CLOSETS. 2017 FBC-PLUMBING SEC.405.3.1. |
| |
| 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| BREWERY TANKS. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 14) SUBMIT A PIPING DETAIL FOR ALL THE PROCESS PIPING |
| FOR ALL THE TANKS INVOLVED IN THE BREWING PROCESS AND |
| THE KEG WASHER. WPB AMEND. TO FBC SEC. 107.2.1. |
| |
| 21) SUBMIT DOCUMENTATION FOR THE TYPE OF WASTE THAT |
| WILL BE DISCHARGED INTO THE TRENCH DRAIN AND ALSO FROM |
| THE KEG WASHER. DEPENDING ON THE TYPE OF WASTE, AN |
| INTERCEPTOR OR SEPARATOR MAY BE REQUIRED IN THE DRAIN |
| LINE FROM THESE AREAS. 2017 FBC-PLUMBING SEC.1003.1. |
| |
| NEW COMMENTS: |
| |
| 1. SHT. A2.2 DETAIL #7 IS SHOWING THE LAVATORY AT |
| 341/2" THE CODE IS 34" MAX PLEASE CLARIFY PER FBC ACC |
| 606.3 |
| |
| 2. SHT. A2.2 DETAIL #7 IS SHOWING THE SIDE GRAB BAR AT |
| 48" OF THE REAR WALL IT SHALL BE 54" MIN PER FBC ACC |
| 604.5.1 |
| |
| 3. SHT. A2.2 THE TOILET PAPER DISPENSER SHALL BE 7-9 |
| OFF THE FRONT OF THE TOILET PER FBC ACC 604.7 |
| |
| 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| |
| 5. THE VENT FOR THE FLOOR SINK THE TRENCH DRAINS ARE |
| DUMPING IS A HORIZONTAL DRY VENT WHICH IS PROHIBITED BY |
| CODE IT SHALL COMPLY WITH FBC PL 905.3 , 905.4 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |