2018-04-05 11:20:03FIRST REVIEW
  
 1). SHOW THE DIMENSIONS OF THE REQUIRED CLEAR FLOOR
 SPACES FOR THE HANDICAPPED ACCESSIBLE FIXTURES. COMPLY
 WITH 2017 FBC-ACCESS. SECS. 604.3 FOR WATER CLOSETS AND
 606.2 AND 305.3 FOR LAVATORIES.
 2) THE HEIGHT OF ACCESSIBLE LAVATORIES SHALL COMPLY
 WITH 2017 FBC-ACCESS. SEC. 606.3.
 3) MIRRORS SHALL COMPLY WITH 2017 FBC-ACCESS. SEC.
 603.3.
 4) THE HEIGHT OF SOAP DISPENSERS, HAND DRYERS, PAPER
 TOWEL DISPENSERS SHALL COMPLY WITH 2017 FBC-ACCESS.
 CODE SEC. 308.
 5) THE LOCATION AND THE HEIGHT OF THE GRAB BARS FOR THE
 WATER CLOSETS SHALL COMPLY WITH 2017 FBC-ACCESS. SECS.
 604.5.1, 604.5.2, 609.4. SHOW THE LOCATION AND MOUNTING
 HEIGHT DIMENSIONS ON THE PLANS.
 6) TOILET PAPER DISPENSERS SHALL BE LOCATED PER 2017
 FBC- ACCESS. SEC. 604.7. SHOW THIS ON THE PLANS
 7) SHT. A2.2 - THE STANDARD TOILET STALL IN THE WOMEN'S
 RESTROOM SHALL BE A MINIMUM OF 60 INCHES FOR FLOOR
 MOUNTED WATER CLOSETS. 2017 FBC-PLUMBING SEC.405.3.1.
 8) PLEASE PROVIDE A LEGEND FOR THE ACRONYMS FOR THE
 TANKS. WPB AMEND. TO FBC SEC. 107.2.1.
 9) INDICATE THE PREVIOUS OCCUPANCY ON THE LIFESAFETY
 PLANS. INDICATE ON THE PLANS IF THIS IS A CHANGE OF
 OCCUPANCY. IF SO, THE STRUCTURE SHALL COMPLY WITH THE
 REQUIREMENTS OF THE 2017 FBC - EXISTING BUILDING CODE.
 10) THE LAVATORY OUTSIDE OF THE TOILET COMPARTMENT
 SHALL COMPLY WITH 2017 FBC-ACCESS. SECS. 213.3.4, 606.
 11) THE URINAL IN THE MEN'S RESTROOM IS LOCATED IN THE
 LINE OF SIGHT OF THE RESTROOM DOOR. IN THE OPEN DOOR
 POSITION, THE USER AT THE URINAL DOES NOT APPEAR TO
 HAVE ADEQUATE PRIVACY AS REQD. IN THE 2017 FBC-PLUMBING
 SEC.405.3.5. SHOW THE LENGTH OF THE URINAL PARTITIONS
 AND THEY SHALL EXTEND FROM THE WALL SURFACE AT EACH
 SIDE OF THE URINAL NOT LESS THAN 18 INCHES OR TO A
 POINT NOT LESS THAN 6 INCHES BEYOND THE OUTERMOST FRONT
 LIP OF THE URINAL MEASURED FROM THE FINISHED BACK WALL
 SURFACE, WHICHEVER IS GREATER.
 12) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 BREWERY TANKS. WPB AMEND. TO FBC SEC. 107.2.1.
 14) SUBMIT A PIPING DETAIL FOR ALL THE PROCESS PIPING
 FOR ALL THE TANKS INVOLVED IN THE BREWING PROCESS AND
 THE KEG WASHER. WPB AMEND. TO FBC SEC. 107.2.1.
 15) THE GAS LINE FROM THE METER TO THE FIRT TEE SHALL
 BE A MINIMUM OF 1 1/2 INCHES PER TABLE 402.4 (2) OF THE
 2017 FBC-FUEL GAS CODE.
 16) THE T & P LINE FROM THE WATER HEATER SHALL
 DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME ROOM
 AS THE WATER HEATER. 2017 FBC-PLUMBING SEC. 504.6 (2).
 17) A BACKFLOW DEVICE IS REQUIRED AT THE METER PER THE
 CITY OF WPB CROSS CONNECTION CONTROL MANUAL. A MINIMUM
 OF A REDUCED PRESSURE ZONE DEVICE IS REQUIRED. A
 SEPARATE PERMIT AND MANUFACTURER'S SPECIFICATIONS SHALL
 BE SUBMITTED FOR REVIEW.
 18) SUBMIT DETAILS FOR THE 8 INCH AND 10 INCH VENTS FOR
 THE BREWHOUSE TANKS SHOWN ON SHT. M-1.
 19) SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
 20) INDIRECT WASTE PIPING THAT EXCEEDS 30 INCHES IN
 DEVELOPED LENGTH MEASURED HORIZONTALLY OR 54 INCHES IN
 TOTAL DEVELOPED LENGTH SHALL BE TRAPPED. 2017
 FBC-PLUMBING SEC.802.2. ( SEE TRENCH DRAINS)
 21) SUBMIT DOCUMENTATION FOR THE TYPE OF WASTE THAT
 WILL BE DISCHARGED INTO THE TRENCH DRAIN AND ALSO FROM
 THE KEG WASHER. DEPENDING ON THE TYPE OF WASTE, AN
 INTERCEPTOR OR SEPARATOR MAY BE REQUIRED IN THE DRAIN
 LINE FROM THESE AREAS. 2017 FBC-PLUMBING SEC.1003.1.
 22) THE HOT WATER RECIRULATION MAIN AND THE FIRST EIGHT
 FEET OF ANY BRANCKES SHALL BE INSULATED WITH INSULATION
 WITH A MINIMUM OF 1 INCH WALL THICKNESS. 2017
 FBC-ENERGY SEC.C404.4.THIS INCLUDES THE RECIRCULATION
 IN THE SLEEVE UNDER THE SLAB.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  