2018-04-05 11:20:03 | FIRST REVIEW |
| |
| 1). SHOW THE DIMENSIONS OF THE REQUIRED CLEAR FLOOR |
| SPACES FOR THE HANDICAPPED ACCESSIBLE FIXTURES. COMPLY |
| WITH 2017 FBC-ACCESS. SECS. 604.3 FOR WATER CLOSETS AND |
| 606.2 AND 305.3 FOR LAVATORIES. |
| 2) THE HEIGHT OF ACCESSIBLE LAVATORIES SHALL COMPLY |
| WITH 2017 FBC-ACCESS. SEC. 606.3. |
| 3) MIRRORS SHALL COMPLY WITH 2017 FBC-ACCESS. SEC. |
| 603.3. |
| 4) THE HEIGHT OF SOAP DISPENSERS, HAND DRYERS, PAPER |
| TOWEL DISPENSERS SHALL COMPLY WITH 2017 FBC-ACCESS. |
| CODE SEC. 308. |
| 5) THE LOCATION AND THE HEIGHT OF THE GRAB BARS FOR THE |
| WATER CLOSETS SHALL COMPLY WITH 2017 FBC-ACCESS. SECS. |
| 604.5.1, 604.5.2, 609.4. SHOW THE LOCATION AND MOUNTING |
| HEIGHT DIMENSIONS ON THE PLANS. |
| 6) TOILET PAPER DISPENSERS SHALL BE LOCATED PER 2017 |
| FBC- ACCESS. SEC. 604.7. SHOW THIS ON THE PLANS |
| 7) SHT. A2.2 - THE STANDARD TOILET STALL IN THE WOMEN'S |
| RESTROOM SHALL BE A MINIMUM OF 60 INCHES FOR FLOOR |
| MOUNTED WATER CLOSETS. 2017 FBC-PLUMBING SEC.405.3.1. |
| 8) PLEASE PROVIDE A LEGEND FOR THE ACRONYMS FOR THE |
| TANKS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 9) INDICATE THE PREVIOUS OCCUPANCY ON THE LIFESAFETY |
| PLANS. INDICATE ON THE PLANS IF THIS IS A CHANGE OF |
| OCCUPANCY. IF SO, THE STRUCTURE SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE 2017 FBC - EXISTING BUILDING CODE. |
| 10) THE LAVATORY OUTSIDE OF THE TOILET COMPARTMENT |
| SHALL COMPLY WITH 2017 FBC-ACCESS. SECS. 213.3.4, 606. |
| 11) THE URINAL IN THE MEN'S RESTROOM IS LOCATED IN THE |
| LINE OF SIGHT OF THE RESTROOM DOOR. IN THE OPEN DOOR |
| POSITION, THE USER AT THE URINAL DOES NOT APPEAR TO |
| HAVE ADEQUATE PRIVACY AS REQD. IN THE 2017 FBC-PLUMBING |
| SEC.405.3.5. SHOW THE LENGTH OF THE URINAL PARTITIONS |
| AND THEY SHALL EXTEND FROM THE WALL SURFACE AT EACH |
| SIDE OF THE URINAL NOT LESS THAN 18 INCHES OR TO A |
| POINT NOT LESS THAN 6 INCHES BEYOND THE OUTERMOST FRONT |
| LIP OF THE URINAL MEASURED FROM THE FINISHED BACK WALL |
| SURFACE, WHICHEVER IS GREATER. |
| 12) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| TANKLESS WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| BREWERY TANKS. WPB AMEND. TO FBC SEC. 107.2.1. |
| 14) SUBMIT A PIPING DETAIL FOR ALL THE PROCESS PIPING |
| FOR ALL THE TANKS INVOLVED IN THE BREWING PROCESS AND |
| THE KEG WASHER. WPB AMEND. TO FBC SEC. 107.2.1. |
| 15) THE GAS LINE FROM THE METER TO THE FIRT TEE SHALL |
| BE A MINIMUM OF 1 1/2 INCHES PER TABLE 402.4 (2) OF THE |
| 2017 FBC-FUEL GAS CODE. |
| 16) THE T & P LINE FROM THE WATER HEATER SHALL |
| DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME ROOM |
| AS THE WATER HEATER. 2017 FBC-PLUMBING SEC. 504.6 (2). |
| 17) A BACKFLOW DEVICE IS REQUIRED AT THE METER PER THE |
| CITY OF WPB CROSS CONNECTION CONTROL MANUAL. A MINIMUM |
| OF A REDUCED PRESSURE ZONE DEVICE IS REQUIRED. A |
| SEPARATE PERMIT AND MANUFACTURER'S SPECIFICATIONS SHALL |
| BE SUBMITTED FOR REVIEW. |
| 18) SUBMIT DETAILS FOR THE 8 INCH AND 10 INCH VENTS FOR |
| THE BREWHOUSE TANKS SHOWN ON SHT. M-1. |
| 19) SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 |
| THROUGH G2439. |
| 20) INDIRECT WASTE PIPING THAT EXCEEDS 30 INCHES IN |
| DEVELOPED LENGTH MEASURED HORIZONTALLY OR 54 INCHES IN |
| TOTAL DEVELOPED LENGTH SHALL BE TRAPPED. 2017 |
| FBC-PLUMBING SEC.802.2. ( SEE TRENCH DRAINS) |
| 21) SUBMIT DOCUMENTATION FOR THE TYPE OF WASTE THAT |
| WILL BE DISCHARGED INTO THE TRENCH DRAIN AND ALSO FROM |
| THE KEG WASHER. DEPENDING ON THE TYPE OF WASTE, AN |
| INTERCEPTOR OR SEPARATOR MAY BE REQUIRED IN THE DRAIN |
| LINE FROM THESE AREAS. 2017 FBC-PLUMBING SEC.1003.1. |
| 22) THE HOT WATER RECIRULATION MAIN AND THE FIRST EIGHT |
| FEET OF ANY BRANCKES SHALL BE INSULATED WITH INSULATION |
| WITH A MINIMUM OF 1 INCH WALL THICKNESS. 2017 |
| FBC-ENERGY SEC.C404.4.THIS INCLUDES THE RECIRCULATION |
| IN THE SLEEVE UNDER THE SLAB. |
| |