2018-04-10 16:13:211ST REVIEW FBC-2017 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #18021224
 4/10/2018
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AND RELOCATED AC SYSTEMS- SECTION C403.2.1 FBC-17
 ENERGY CONSERVATION. PLEASE NOTE THAT BECAUSE THIS IS A
 CHANGE OF OCCUPANCY WITH NEW HEAT PRODUCING BREWERY
 EQUIPMENT, IT IS NECESSARY TO PROVIDE NEW HEAT LOAD
 CALCS TO VERIFY SYSTEM SIZING.
  
 2) M-1: PROVIDE AN UP-TO-DATE SURVEY THAT INDICATES THE
 PROPERTY LINE OR RIGHT OF WAY ON THE WEST SIDE OF THE
 BUILDING THE M-1 PLAN SHOWS THE AC CONDENSERS, THE
 CHILLER, AND THE O/A INTAKES ON THAT SIDE OF THE
 BUILDING. PLEASE NOTE THAT O/A INTAKES SHALL BE LOCATED
 NOT LESS THAN 10' FROM LOT LINES PER SECTION 401.4.
  
 3) M-1 & M-2: INDICATE THE TYPE AND SIZE OF THE GLYCOL
 PIPING, THE TYPE AND THICKNESS OF THE PIPE INSULATIONS,
 AND THE SPACING OF THE PIPE SUPPORT STANDS.
  
 4) M-2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE CHILLER
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 5) M-2: PROVIDE THE OUTSIDE AIR CFMS FOR AHU-2 & 3 IN
 THE EQUIPMENT SCHEDULE.
  
 6) M-1 & M-2: PROVIDE THE WIND DESIGN CRITERIA USED TO
 DETERMINE THE PRESSURES AND ANCHORING AND FASTENING
 METHODS FOR ALL OF THE EXTERIOR MECHANICAL EQUIPMENT
 AND COMPONENTS- SECTION 301.15
  
 7) M-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 BREWHOUSE TANK- SECTION 304 FBC-17 FUEL GAS.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE BREWERY TANKS WITH
 APPROVAL STAMPS BY THE DESIGNER OF RECORD. REFER TO
 SECTION1003.1 FBC-17 MECHANICAL: IF THE TANKS ARE
 DETERMINED TO BE CLASSIFIED AS PRESSURE VESSELS, THEY
 SHALL BE CONSTRUCTED AND CERTIFIED IN ACCORDANCE WITH
 ASME BOILER AND PRESSURE VESSEL CODE.
  
 9) IDENTIFY AND LABEL ALL THE BREWERY TANKS AND
 EQUIPMENT SHOWN ON THE PLAN PROVIDE A PROCESS PIPING
 PLAN AND ISOMETRIC DRAWING.
  
 10) THE PROPOSED OCCUPANCY SHALL BE IN COMPLIANCE WITH
 SECTION C505.1 FBC-17 ENERGY CONSERVATIONS. PLEASE
 PROVIDE A COMPLIANCE REPORT AS REQUIRED BY SECTION
 C101.5.
  
 11) PROVIDE A FLORIDA PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE O/A LOUVERS- RULE 9N-3 FAC.
  