2018-03-27 15:14:53 | PERMIT # 18021224 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| FAILED COMMENTS: |
| |
| 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION |
| SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? |
| |
| 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| SYSTEM AND/OR FIRE ALARM SYSTEM. |
| |
| 4) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| 5) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN |
| OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER |
| THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE |
| PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER |
| LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR |
| PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE |
| AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A |
| READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN |
| UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS |
| SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE |
| EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH |
| AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK |
| IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK. |
| |
| 6) TWO MEANS OF EGRESS IS REQUIRED, HOWEVER ASSEMBLY |
| MAY NOT EGRESS THROUGH A HIGHER HAZARD AREA |
| (F-2/INDUSTRIAL). PLEASE REVIEW AND PROVIDE A 2ND MEANS |
| OF EGRESS FOR THE ASSEMBLY OCCUPANCY OF THE BUILDING. |
| |
| 7) ADDITIONAL EXIT AND EXIT DIRECTIONAL SIGNAGE MAY BE |
| REQUIRED. THIS WILL BE VERIFIED IN THE FIELD. |
| |
| 8) PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATION |
| SHEETS FOR ALL OF THE EQUIPMENT THAT WILL BE HOUSED AND |
| UTILIZED IN THE F-2 OCCUPANCY OF THIS LOCATION TO |
| BETTER DETERMINE CLASSIFICATION OF HAZARD OF CONTENTS. |
| PLEASE LABEL LOCATION OF EACH TYPE OF EQUIPMENT ON THE |
| LIFE SAFETY SHEET OR A SEPARATE EQUIPMENT LAYOUT SHEET. |
| |
| 9) PLEASE INCLUDE A NARRATIVE EXPLAINING THE BREWING |
| PROCESS AND ORDER OF OPERATIONS. |
| |
| ADDITIONAL COMMENTS MAY BE PROVIDED AFTER RECEIPT AND |
| REVIEW OF RESUBMISSION. |
| |
| |