Plan Review Notes
Plan Review Notes For Permit 18021224
Permit Number 18021224
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-03-27 15:14:53PERMIT # 18021224
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 5) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
 6) TWO MEANS OF EGRESS IS REQUIRED, HOWEVER ASSEMBLY
 MAY NOT EGRESS THROUGH A HIGHER HAZARD AREA
 (F-2/INDUSTRIAL). PLEASE REVIEW AND PROVIDE A 2ND MEANS
 OF EGRESS FOR THE ASSEMBLY OCCUPANCY OF THE BUILDING.
  
 7) ADDITIONAL EXIT AND EXIT DIRECTIONAL SIGNAGE MAY BE
 REQUIRED. THIS WILL BE VERIFIED IN THE FIELD.
  
 8) PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATION
 SHEETS FOR ALL OF THE EQUIPMENT THAT WILL BE HOUSED AND
 UTILIZED IN THE F-2 OCCUPANCY OF THIS LOCATION TO
 BETTER DETERMINE CLASSIFICATION OF HAZARD OF CONTENTS.
 PLEASE LABEL LOCATION OF EACH TYPE OF EQUIPMENT ON THE
 LIFE SAFETY SHEET OR A SEPARATE EQUIPMENT LAYOUT SHEET.
  
 9) PLEASE INCLUDE A NARRATIVE EXPLAINING THE BREWING
 PROCESS AND ORDER OF OPERATIONS.
  
 ADDITIONAL COMMENTS MAY BE PROVIDED AFTER RECEIPT AND
 REVIEW OF RESUBMISSION.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  