 RISER DIAGRAM AND FLOOR PLAN SHOW SERVICE IN AN OTHER
 SPACE. IS THIS SPACE PART OF THIS OCCUPANCY?
  
 IF NOT SERVICE CANNOT BE IN AN OTHER SPACE MUST BE
 ACCESSIBLE TO ALL TENNANTS.
 230.72 (C) ACCESS TO OCCUPANTS. IN A MULTIPLE-OCCUPANCY
 BUILDING,
 EACH OCCUPANT SHALL HAVE ACCESS TO THE OCCUPANT?S
 SERVICE DISCONNECTING
 MEANS.
  
 110.24 FAULT CURRNET CALCULATION REQUIRED FOR THE
 SERVICE AND PANELS.