Plan Review Notes
Plan Review Notes For Permit 18021224
Permit Number 18021224
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-27 14:15:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18021224
 ADD: 425 KANUGA RD.
 CONT: PERK CONSTRUCTION
 TEL: 561-401-5984
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 27/2018
 ACTION: DENIED
  
 1) SHEET 006-LS2.1:
 1A) UNDER THE CODE ANALYSIS THE PLANS INDICATE THIS IS
 A LEVEL 3 ALTERATION. PLEASE NOTE THIS BUILDING IS A
 MIXED USE OCCUPANCY AS STATED IN THE PLANS AND WILL
 ALSO NEED TO SHOW COMPLIANCE WITH THE 2017 EXISTING
 BUILDING CODE SECTION 1001.2.2.1 PARTIAL CHANGE OF
 OCCUPANCY. WHERE THE OCCUPANCY CLASSIFICATION OR GROUP
 OF A PORTION OF AN EXISTING BUILDING IS CHANGED,
 SECTION 1012 SHALL APPLY.
  
 1B) 2017 EXIST. BLDG. CODE 1012.4 MEANS OF EGRESS,
 GENERAL. HAZARD CATEGORIES IN REGARD TO LIFE SAFETY AND
 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH TABLE
 1012.4.
  
 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY. WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS
 MADE TO A HIGHER HAZARD CATEGORY (LOWER NUMBER) AS
 SHOWN IN TABLE 1012.4, THE MEANS OF EGRESS SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 FOR THE A-2 OCCUPANCY THE OCCUPANT LOAD IS OVER 50
 WHICH REQUIRE (2) MEANS OF EGRESS. EVEN THOUGH THIS IS
 A MIXED OCCUPANCY NON-SEPARATED YOU CANNOT TAKE THE A2
 OCCUPANTS INTO THE HIGHER HAZARD F2 OCCUPANCY. PLEASE
 REVIEW 2017 FBC-B SECTION 1016.2 EGRESS THROUGH
 INTERVENING SPACES.
 EXCEPTION: MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 ADJOINING OR INTERVENING ROOMS OR SPACES IN GROUP H, S
 OR F OCCUPANCY WHERE THE ADJOINING OR INTERVENING ROOMS
 OR SPACES ARE THE SAME OR A LESSER HAZARD OCCUPANCY
 GROUP.
 PLEASE PROVIDE THE 2ND MEANS OF EGRESS FOR THE A-2
 OCCUPANCY WITHOUT GOING THROUGH THE F-2 OCCUPANCY.
  
 1C) THE LS2.1 SHEET UNDER THE HEADING MINIMUM NUMBER OF
 EXITS ALSO INDICATES 50% OF THE EXITS ARE ACCESSIBLE.
 2017 EXISTING BUILDING CODE SECTION 1012.1.4
 ACCESSIBILITY. ALL BUILDINGS UNDERGOING A CHANGE OF
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 1012.8. 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT
 UNDERGO A CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION
 SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 2017 FBC-ACCESSIBILITY CODE. 206.4.1 PUBLIC ENTRANCES.
 (DOORWAYS). IN ADDITION TO ENTRANCES REQUIRED BY
 206.4.2 THROUGH 206.4.9, AT LEAST 60 PERCENT (2 X 0.60
 = 1.2 OR 2) OF ALL PUBLIC ENTRANCES SHALL COMPLY WITH
 404. BARRIERS AT COMMON OR EMERGENCY ENTRANCES AND
 EXITS OF BUSINESS ESTABLISHMENTS CONDUCTING BUSINESS
 WITH THE GENERAL PUBLIC THAT ARE EXISTING, UNDER
 CONSTRUCTION, OR UNDER CONTRACT FOR CONSTRUCTION WHICH
 WOULD PREVENT A PERSON FROM USING SUCH ENTRANCES OR
 EXITS SHALL BE REMOVED. PLEASE SHOW WHERE THE 2ND
 ACCESSIBLE MEANS OF EGRESS WILL BE LOCATED AND NOT IN
 THE F-2 OCCUPANCY.
  
 1D) THE LS2.1 SHEET UNDER THE CODE ANALYSIS/ TOTAL
 NUMBER OF OCCUPANTS NEEDS TO CORRECT THE A-2 OCCUPANT
 LOAD. 1,578 SQ. FT. / 15 = 105.2 OR 106 OCCUPANT LOAD,
 YOU ALWAYS ROUND UP ON OCCUPANTS TO THE NEXT WHOLE
 NUMBER. FBC-B TABLE 1004.1.2.
  
 1E) SHEET LS2.1 UNDER THE HEADING FIRE RESISTANCE
 RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON
 SEPARATION DISTANCE (TABLE 602). PLEASE PROVIDE A
 SURVEY SHOWING THE DISTANCE FROM BOTH THE REAR WALL AND
 WALL CLOSEST TO THE RAILROAD TRACKS.
 2017 EXISTING BUILDING CODE 1012.6 EXTERIOR WALL
 FIRE-RESISTANCE RATINGS. HAZARD CATEGORIES IN REGARD TO
 FIRE-RESISTANCE RATINGS OF EXTERIOR WALLS SHALL BE IN
 ACCORDANCE WITH TABLE 1012.6.
 1012.6.1 EXTERIOR WALL RATING FOR CHANGE OF OCCUPANCY
 CLASSIFICATION TO A HIGHER HAZARD CATEGORY.
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY AS SHOWN IN TABLE 1012.6,
 EXTERIOR WALLS SHALL HAVE FIRE RESISTANCE AND EXTERIOR
 OPENING PROTECTIVES AS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING.
  
 1F) SHEET LS2.1 SHOW COMPLIANCE WITH: 2017 EXISTING
 BUILDING CODE SECTION 1012.6.3 OPENING PROTECTIVES.
 OPENINGS IN EXTERIOR WALLS SHALL BE PROTECTED AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING. WHERE
 OPENINGS IN THE EXTERIOR WALLS ARE REQUIRED TO BE
 PROTECTED BECAUSE OF THEIR DISTANCE FROM THE LOT LINE,
 THE SUM OF THE AREA OF SUCH OPENINGS SHALL NOT EXCEED
 50 PERCENT OF THE TOTAL AREA OF THE WALL IN EACH STORY.
 2017 FBC-B TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE
 OF OPENING PROTECTION.
  
 1G) THE LS2.1 SHEET SHOWS THE PROPOSED EXITS, BUT DOES
 NOT PROVIDE COMPLIANCE WITH 2017 FBC-B SECTION 1028.5
 ACCESS TO A PUBLIC WAY. THE EXIT DISCHARGE SHALL
 PROVIDE A DIRECT AND UNOBSTRUCTED ACCESS TO A PUBLIC
 WAY.
  
 1H) THE LS2.1 SHEET INDICATES THE USE OF A LIFT. PLEASE
 PROVIDE THE ASME STANDARD THIS LIFT IS TO BE DESIGNED
 TOO? PLEASE ALSO PROVIDE THE MANUFACTURES SPEC ON THIS
 LIFT.
 2017 ACCESSIBILITY CODE SECTIONS:
 408.1 LIMITED-USE/LIMITED-APPLICATION ELEVATORS SHALL
 COMPLY WITH 408 AND WITH ASME A17.1 (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
 THEY SHALL BE PASSENGER ELEVATORS AS CLASSIFIED BY ASME
 A17.1. ELEVATOR OPERATION SHALL BE AUTOMATIC.
 410.1. PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1
 (1999 EDITION OR 2003 EDITION) (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
 PLATFORM LIFTS SHALL NOT BE ATTENDANT-OPERATED AND
 SHALL PROVIDE UNASSISTED ENTRY AND EXIT FROM THE LIFT.
  
 1I) THE LS2.1 SHEET WILL NEED TO HAVE MORE EXIT
 DIRECTIONAL LIGHT TO COMPLY WITH THE 2017 FBC-B 1013.1.
 WHERE REQUIRED. THE PATH OF EGRESS TRAVEL TO EXITS AND
 WITHIN EXITS SHALL BE MARKED BY READILY VISIBLE EXIT
 SIGNS TO CLEARLY INDICATE THE DIRECTION OF EGRESS
 TRAVEL IN CASES WHERE THE EXIT OR THE PATH OF EGRESS
 TRAVEL IS NOT IMMEDIATELY VISIBLE TO THE OCCUPANTS.
 INTERVENING MEANS OF EGRESS DOORS WITHIN EXITS SHALL BE
 MARKED BY EXIT SIGNS. EXIT SIGN PLACEMENT SHALL BE SUCH
 THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT
 PASSAGEWAY IS MORE THAN 100 FEET (30 480 MM) OR THE
 LISTED VIEWING DISTANCE FOR THE SIGN, WHICHEVER IS
 LESS, FROM THE NEAREST VISIBLE EXIT SIGN.
  
 2) THE LIFE SAFETY SHEET LS2.1 DOES NOT SHOW COMPLIANCE
 WITH THE 2014 FBC-ACCESSIBILITY CODE;
 2A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 2B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 2C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, AND BARS INCLUDING
 RAISED OR SUNKEN DINING AREAS, AND OUTDOOR DINING
 AREAS.
  
 2D) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 2D)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 2D)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 3) SHEET 003-A2.
 3A) IN THE BOTTOM RIGHT OF THE SHEET THERE IS A NEW
 STAIRS. SHEET 004 A2.2 DETAIL 4 IS OF THE STAIRS AND
 GUARD/HAND RAIL SYSTEMS. THE PLANS ARE SILENT AS TO THE
 TYPE OF FRAMING THAT IS ANCHORED TO THE FLOOR AND THE
 TYPE OF ANCHORS, SIZE AND QUANTITY OF ANCHORS FOR THE
 FLOOR FRAMING AND WALL FRAMING THE STAIRS ARE ANCHORED
 TOO? 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 3B) IN THE BOTTOM RIGHT OF THE SHEET THERE IS A NEW
 STAIRS. SHEET 004 A2.2 DETAIL 4 IS OF THE STAIRS AND
 GUARD/HAND RAIL SYSTEMS. THE PLANS ARE SILENT AS TO THE
 TYPE OF MATERIAL THE GUARDRAIL AND HANDRAIL SYSTEMS ARE
 MADE. THE PLANS DO NOT INDICATE HOW THEY ARE ANCHORED
 TO THE FLOOR?
  
 3B)(1)1607.8.1 HANDRAILS AND GUARDS. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A LINEAR LOAD OF 50
 POUNDS PER LINEAR FOOT (PLF) IN ACCORDANCE WITH SECTION
 4.5.1 OF ASCE 7.
  
 3B)(2) 1607.8.1.1 CONCENTRATED LOAD. HANDRAILS AND
 GUARDS SHALL BE DESIGNED TO RESIST A CONCENTRATED LOAD
 OF 200 POUNDS IN ACCORDANCE WITH SECTION 4.5.1 OF ASCE
 7.
  
 3B)(3) 1607.8.1.2 INTERMEDIATE RAILS. INTERMEDIATE
 RAILS (ALL THOSE EXCEPT THE HANDRAIL), BALUSTERS AND
 PANEL FILLERS SHALL BE DESIGNED TO RESIST A
 CONCENTRATED LOAD OF 50 POUNDS IN ACCORDANCE WITH
 SECTION 4.5.1 OF ASCE 7.
  
 4) SHEET 033A2.1 INDICATES THE USE OF OVERHEAD DOORS
 WITH GLASS PANELS IDENTIFIED AS DOOR # 2. PLEASE SHOW
 COMPLIANCE WITH 2017 FBC-B 2405.2 ALLOWABLE GLAZING
 MATERIALS AND LIMITATIONS. SLOPED GLAZING SHALL BE ANY
 OF THE FOLLOWING MATERIALS, SUBJECT TO THE LISTED
 LIMITATIONS.
 4.1.FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING
 MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE
 LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM)
 POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED
 GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE
 REQUIREMENTS OF SECTION 2607, HEAT-STRENGTHENED GLASS
 OR FULLY TEMPERED GLASS.
  
  
 4.2. FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT OR
 LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED IN
 EXCEPTIONS 2 AND 3 OF SECTION 2405.3.
 FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE
 SECTION 2610. GLASS-BLOCK CONSTRUCTION SHALL CONFORM TO
 THE REQUIREMENTS OF SECTION 2110.1.
  
 THE SUBMITTED PRODUCT APPROVAL FL 16549-R9 IS FOR A
 CLOPAY OVERHEAD GARAGE DOOR.
 SHEET 2 OF 7 IDENTIFY WHICH MODEL, NUMBER AND NAME OF
 DOOR TO BE INSTALLED.
 SHEET 3 OF 7. PLEASE IDENTIFY THE BRAND AND IF THE DOOR
 IS MODERN STEEL OR COMMERCIAL DOORS, IDENTIFY THE SIZE
 OF PANEL FOR THE IMPACT RESISTANT GLAZING. ALSO
 IDENTIFY BOTTOM CENTER GLAZING PATTERN TO BE INSTALLED.
 SHEET 2 OF 5 DWG. B. IMPACT RESISTANT CONSTRUCTION
 PLEASE IDENTIFY THE TYPE OF GLAZING TO BE INSTALLED TO
 MEET THE WIND LOAD TESTING AND SAFETY GLAZING
 REQUIREMENTS OF FBC-B 2405.2 AND OR 2606.
  
 5) SHEET 005A2.3 EXTERIOR ELEVATIONS;
 5A) THE ENGINEERING CRITERIA LIST THE WIND EXPOSURE AS
 AN EXPOSURE B. THE VULT AND VASD WIND SPEEDS ARE BOTH
 EXPRESSED, BUT THE PRESSURES GIVEN DO NOT STATE IF THEY
 ARE IN VULT OR VASD? 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 5B) THE SOUTH ELEVATION SHOWS THE NEW STOREFRONT ENTRY
 WITH TRANSOM, SIDE LIGHTS, BOTH VERTICAL AND HORIZONTAL
 MULLIONS AND STOREFRONT DOORS. PLEASE PROVIDE
 DOCUMENTATION OF CODE COMPLIANCE WITH:
  
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
  
 5C) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5D) THRESHOLDS ACCESS. CODE 404.2.5. THRESHOLDS, IF
 PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH
 MAXIMUM. RAISED THRESHOLDS AND CHANGES IN LEVEL AT
 DOORWAYS SHALL COMPLY WITH 302 AND 303.
  
 5E) MULTICERAMICS EZ ROOF SYSTEM IS A
 CONTINUOUS-FILAMENT, SINGLE-PLY, FLUID APPLIED ROOFING
 SYSTEM. PLEASE PROVIDE COMPLIANCE WITH 2017 FBC-B
 1507.15 LIQUID-APPLIED ROOFING. THE INSTALLATION OF
 LIQUID-APPLIED ROOFING SHALL COMPLY WITH THE PROVISIONS
 OF THIS SECTION.
  
 5E)(1)1507.15.1 SLOPE. LIQUID-APPLIED ROOFING SHALL
 HAVE A DESIGN SLOPE OF NOT LESS THAN ONE-FOURTH UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE).
  
 5E)(2) 1507.15.2 MATERIAL STANDARDS. LIQUID-APPLIED
 ROOFING SHALL COMPLY WITH ASTM C836, ASTM C957, ASTM
 D1227 OR ASTM D3468, ASTM D6083, ASTM D6694 OR ASTM
 D6947.
  
 5F) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) BOTH THE LIFE SAFETY SHEET AND 003A2.1 SHOW THE
 BREWHOUSE ON THE THICKENED SLAB, BUT NO OTHER
 INFORMATION IS GIVEN TO THE PLATFORM, LANDING GUARDRAIL
 NOR HANDRAIL.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 7. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 CONSTRUCTION / STRUCTURAL REQUIREMENTS FOR :
 PLATFORMS SHOW COMPLIANCE WITH FBC-B 410.4.
 STAIRS FBC-B 1011.7 STAIRWAY CONSTRUCTION / LIVE LOADS
 TABLE 1607.1.
 GUARDRAILS / HANDRAILS
 1607.8.1HANDRAILS AND GUARDS.
 1607.8.1.1 CONCENTRATED LOAD.
 1607.8.1.2 INTERMEDIATE RAILS.
  
 7) 004A2.2 DETAILS 2 & 3 HAVE PROVIDED THE HORIZONTAL
 DISTANCES APART BUT THE DETAILS DO NOT PROVIDE THE
 REQUIRED HEIGHT FOR THE ACCESSIBLE ELEMENTS;
 WATER CLOSET
 GRAB BARS
 SINK
 URINAL
 MIRROR
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED TO
 DETERMINE CODE COMPLIANCE.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 ,
  