2019-01-29 16:37:39 | ****CORRECTIONS**** |
| |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| FBC 107. PLEASE PROVIDE MORE INFORMATION: |
| |
| 1A OK |
| 1B OK |
| |
| 1C (FBC B 505.2.1), (PAGES LS-1, A-1, S-1,& E-1) THE |
| SECOND FLOOR STILL DOES NOT MEET THE CRITERIA OF A |
| MEZZANINE. WE MAY BE ABLE TO LABEL THE SECOND FLOOR AS |
| A MEZZANINE IF THE WALL SEPERATING THE EXISTING |
| BUILDING FROM THE PROPOSED NEW SECTION HAS AN OPENING |
| (LARGER THAN THE DOORWAY) TO CLEARLY COMBINE THE TWO |
| AREAS AS ONE. |
| |
| 2. OK |
| 3. & 4. OK THE STRUCTURE AT THE FRONT ENTRY AREA DOES |
| NOT EXIST, PER THE CONTRACTOR AND THE STRUCTURE AT THE |
| ADJACENT LOT TO THE WEST IS TO BE REMOVED THROUGH THE |
| DEMO PERMIT # 18111011. |
| |
| 5A & 5C (FBC B 107.3.5(4)/FBC B 704/FBC B 705), (PAGES |
| A-1 & S-1) SPECIFIC DETAILS ARE NEEDED (AN APPROVED |
| ASSEMBLY) ON HOW THE THREE HOUR FIRE RATING WILL BE |
| ACHIEVED AT THE 8" CMU WALL. |
| |
| 5B OK |
| |
| 6. (FBC B 505.2.1), (PAGES LS-1, A-1, S-1 & E-1) SAME |
| AS ITEM 1C (MEZZANINE). |
| |
| 7. (FBC B 1014) (PAGE A-1) PROVIDE A DETAIL FOR THE |
| HAND RAIL IN ADDITION TO THE GUARD RAIL FOR THE STAIRS. |
| |
| 8, 9, 10, 11, 12, 13, & 14. OK |
| |
| 15. COUNTY IMPACT FEES, TO BE PAID PRIOR TO COMPLETE |
| PERMIT APPROVAL. |
| |
| 16. OK |
| |
| 17. MISSING THE RESIDENT INSPECTOR FORM. |
| |
| |