Plan Review Notes For Permit 18021186
Permit Number 18021186
Review Stop M
Sequence Number 2
Notes
Date Text
2018-09-25 16:32:282ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18021186
 9/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET E-1: THE VENTILATION SCHEDULE SHOWS NO O/A
 PROVIDED TO THE WAREHOUSE, AND THE PLAN SHOWS AN
 UNDERSIZED EXHAUST FAN AND NO MEANS OF PROVIDING MAKEUP
 AIR OR CROSS-VENTILATION.
  
 2) E-1: PLEASE PROVIDE ELEVATION DRAWINGS OF THE
 CARPORT TO VERIFY THAT IT MEETS THE CRITERIA OF AN OPEN
 PARKING GARAGE AS DEFINED IN SECTION 406.5.2 FBC B.
  
 3) E-1: OPENING PROTECTION REQUIRED AT THE NEW EXHAUST
 FAN LOCATION IN THE WALL- SECTION 1609.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  