Plan Review Notes For Permit 18021186 |
Permit Number |
18021186 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-09-25 16:32:28 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #18021186 | | 9/25/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET E-1: THE VENTILATION SCHEDULE SHOWS NO O/A | | PROVIDED TO THE WAREHOUSE, AND THE PLAN SHOWS AN | | UNDERSIZED EXHAUST FAN AND NO MEANS OF PROVIDING MAKEUP | | AIR OR CROSS-VENTILATION. | | | | 2) E-1: PLEASE PROVIDE ELEVATION DRAWINGS OF THE | | CARPORT TO VERIFY THAT IT MEETS THE CRITERIA OF AN OPEN | | PARKING GARAGE AS DEFINED IN SECTION 406.5.2 FBC B. | | | | 3) E-1: OPENING PROTECTION REQUIRED AT THE NEW EXHAUST | | FAN LOCATION IN THE WALL- SECTION 1609.1.2 FBC B. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|