2018-10-29 09:34:33 | ****CORRECTIONS**** |
| |
| PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6673 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| BUILDING REVIEW FROM FASTRACK RESPONSE LIST: |
| |
| 1.A. (OK). |
| 1.B. (OK). |
| 1.C. (PENDING PER FBC 505.2.1)(PAGES LS-1, A-1, S-1, & |
| E-1) THIS ROOM DOES NOT APPEAR TO MEET THE CRITERIA FOR |
| MEZZANINE. THE ROOM DESIGNATION NEEDS TO BE CHANGED ON |
| PLANS. |
| 2. (OK). |
| 3. AND 4. (PENDING PER FBC 705.2) (PAGE LS-1) THE |
| BUILDING AT FRONT ENTRANCE DOES NOT EXIST, PER THE |
| CONTRACTOR. A CORRECTION OF THE BOUNDARIES SEPERATING |
| THE TWO LOTS ON THE EXISTING SITE PLAN SHOWN ON PAGE |
| LS-1 IS REQUIRED. AS FAR AS THE ADJOINING LOT ATTACHED |
| ROOF/COVERED AREA GOES, THERE ARE TWO OPTIONS: |
| 1. APPLY FOR DEMO PERMIT TO REMOVE THE STRUCTURE OR, |
| 2. APPLY TO THE CITY ENGINEERING DEPARTMENT (USING THE |
| APPLICATION FOR UNITY OF TITLE) FOR A UNITY OF CONTROL |
| PERMIT IN LIEU OF A UNITY OF TITLE PERMIT. THIS |
| APPROVAL MAY ALLOW YOU TO KEEP DEVELOPMENT RIGHTS. |
| 5.A. (PENDING PER FBC 107.3.5(4)/FBC 704/FBC 705) (PAGE |
| A-1 & S-1) PROVIDE DETAILS SHOWING HOW THE 8? CMU WALL |
| IS RATED FOR 3 HOURS. |
| 5.B. (OK) THE NEW WEST WALL IS NOT ON THE PROPERTY |
| LINE. |
| 5.B.1 (OK) NO OPENINGS ON THE WEST SIDE OF THE ADJACENT |
| BUILDING TO THE EAST, PER THE CONTRACTOR. |
| 5.C. (PENDING FBC 107.3.5(4)/FBC 704/FBC 705) (PAGE A-1 |
| & S-1) PROVIDE DETAILS SHOWING HOW THE 8? CMU WALLS ARE |
| RATED FOR 3 HOURS. |
| 6. (PENDING FBC 505.2.1) (PAGE LS-1, A-1, S-1, & E-1) |
| THE AREA LABELED AS MEZZANINE DOES NOT APPEAR TO MEET |
| THE CRITERIA OF MEZZANINE PER FBC 505.2.1. PLEASE |
| REVIEW & RESUBMIT. |
| 7. (PENDING FBC 1014) (PAGE A-1) THE LANDING IS NOW |
| SHOWN ON PLAN. PROVIDE DETAIL FOR HAND RAIL IN ADDITION |
| TO GUARD DETAIL. |
| 8. (PENDING FBC TABLE 1006.2.1) (PAGE LS-1) PROVIDE |
| ACTUAL TRAVEL DISTANCE ON LIFE SAFETY PLAN AND SHOW |
| RACKING/SHELVING LAYOUT. |
| 9. (PENDING FBC 107) (PAGE A-2) PROVIDE THE PRODUCT |
| APPROVAL FOR WHAT APPEARS TO BE A MULLION BAR BETWEEN |
| FIXED WINDOWS AT 2ND LEVEL WEST ELEVATION. |
| 10. ? 14. (OK) |
| 15. (PENDING) IMPACT FEES WILL BE PAID TO THE COUNTY |
| UPON APPROVAL OF PLANS. |
| 16. (OK). |
| 17. (PENDING) STILL NEED THE RESIDENT INSPECTOR |
| APPLICATION. |
| |