2018-03-15 08:49:45 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18021186 | | 3/15/18 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR REVIEW. | | PLEASE INDICATE HOW THE WAREHOUSE, MEZZANINE, AND | | TOILET ROOM WILL BE VENTILATED- REFER TO SECTION 401.2. | | DEPENDING ON WHICH METHOD IS TO BE USED- EITHER NATURAL | | OR MECHANCIAL- VENTILATION CALCULATIONS SHALL BE | | PROVIDED IN ACCORDANCE WITH SECTION 402.2 OR TABLE | | 403.1.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|