Plan Review Notes
Plan Review Notes For Permit 18021186
Permit Number 18021186
Review Stop M
Sequence Number 1
Notes
Date Text
2018-03-15 08:49:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18021186
 3/15/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR REVIEW.
 PLEASE INDICATE HOW THE WAREHOUSE, MEZZANINE, AND
 TOILET ROOM WILL BE VENTILATED- REFER TO SECTION 401.2.
 DEPENDING ON WHICH METHOD IS TO BE USED- EITHER NATURAL
 OR MECHANCIAL- VENTILATION CALCULATIONS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 402.2 OR TABLE
 403.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  