Plan Review Notes
Plan Review Notes For Permit 18021185
Permit Number 18021185
Review Stop B
Sequence Number 1
Notes
Date Text
2018-03-02 09:45:44 
 BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THIS REVISION IS A CHANGE IN THE SCOPE OF WORK FOR
 PERMIT #17111074 WHERE 17 WINDOWS AND 1 DOOR ARE TO BE
 REPLACED.
 2. THE EXCEPTION TO OPENING PROTECTION AFFORDED IN THE
 FBC EXISTING BLDG. SECTION 707.4 DOES NOT APPLY DUE TO
 THE FACT THAT MORE THAN 25% OF THE AGGREGATE GLAZING IS
 TO BE REPLACED.
 3. PROVIDE EITHER A PRODUCT APPROVAL FOR AN IMPACT
 RATED WINDOW FOR THIS LOCATION OR PROVIDE OPENING
 PROTECTION.
  
 FBC EXISTING
 SECTION 707.4 REPLACEMENT OF WINDOWS AND DOORS.
  
 THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS,
 SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL
 BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 EXCEPTIONS:
  
 1.OPENING PROTECTION EXCEPTION: FOR ONE- AND TWO FAMILY
 DWELLINGS CONSTRUCTED UNDER CODES OTHER THAN THE
 FLORIDA BUILDING CODE AND LOCATED IN WINDBORNE DEBRIS
 REGIONS, THE REPLACEMENT OF GARAGE DOORS AND EXTERIOR
 DOORS WITH GLAZING, SLIDING GLASS DOORS, GLASS PATIO
 DOORS, SKYLIGHTS, AND OPERABLE AND INOPERABLE WINDOWS
 WITHIN ANY 12-MONTH PERIOD SHALL NOT BE REQUIRED TO
 HAVE OPENING PROTECTION BUT SHALL BE DESIGNED FOR WIND
 PRESSURES FOR ENCLOSED BUILDINGS, PROVIDED THE
 AGGREGATE AREA OF THE GLAZING IN THE REPLACED
 COMPONENTS DOES NOT EXCEED 25 PERCENT OF THE AGGREGATE
 AREA OF THE GLAZED OPENINGS IN THE DWELLING OR DWELLING
 UNIT.
  
 2.OPENING PROTECTION EXCEPTION FOR HIGH-VELOCITY
 HURRICANE ZONES: FOR ONE- AND TWO-FAMILY DWELLINGS
 CONSTRUCTED UNDER CODES PRIOR TO SEPTEMBER 1, 1994 THE
 REPLACEMENT OF EXTERIOR DOORS WITH GLAZING, SLIDING
 GLASS DOORS, GLASS PATIO DOORS, SKYLIGHTS, AND OPERABLE
 AND INOPERABLE WINDOWS WITHIN ANY 12 MONTH PERIOD SHALL
 NOT BE REQUIRED TO HAVE OPENING PROTECTION PROVIDED THE
 AGGREGATE AREA OF THE GLAZING IN THE REPLACED
 COMPONENTS DOES NOT EXCEED 25 PERCENT OF THE AGGREGATE
 AREA OF THE GLAZED OPENINGS IN THE DWELLING OR DWELLING
 UNIT
  
  