| BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2010 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. THIS REVISION IS A CHANGE IN THE SCOPE OF WORK FOR |
| PERMIT #17111074 WHERE 17 WINDOWS AND 1 DOOR ARE TO BE |
| REPLACED. |
| 2. THE EXCEPTION TO OPENING PROTECTION AFFORDED IN THE |
| FBC EXISTING BLDG. SECTION 707.4 DOES NOT APPLY DUE TO |
| THE FACT THAT MORE THAN 25% OF THE AGGREGATE GLAZING IS |
| TO BE REPLACED. |
| 3. PROVIDE EITHER A PRODUCT APPROVAL FOR AN IMPACT |
| RATED WINDOW FOR THIS LOCATION OR PROVIDE OPENING |
| PROTECTION. |
| |
| FBC EXISTING |
| SECTION 707.4 REPLACEMENT OF WINDOWS AND DOORS. |
| |
| THE REPLACEMENT OF GARAGE DOORS, EXTERIOR DOORS, |
| SKYLIGHTS, AND OPERATIVE AND INOPERATIVE WINDOWS SHALL |
| BE DESIGNED AND CONSTRUCTED TO COMPLY WITH CHAPTER 16 |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| EXCEPTIONS: |
| |
| 1.OPENING PROTECTION EXCEPTION: FOR ONE- AND TWO FAMILY |
| DWELLINGS CONSTRUCTED UNDER CODES OTHER THAN THE |
| FLORIDA BUILDING CODE AND LOCATED IN WINDBORNE DEBRIS |
| REGIONS, THE REPLACEMENT OF GARAGE DOORS AND EXTERIOR |
| DOORS WITH GLAZING, SLIDING GLASS DOORS, GLASS PATIO |
| DOORS, SKYLIGHTS, AND OPERABLE AND INOPERABLE WINDOWS |
| WITHIN ANY 12-MONTH PERIOD SHALL NOT BE REQUIRED TO |
| HAVE OPENING PROTECTION BUT SHALL BE DESIGNED FOR WIND |
| PRESSURES FOR ENCLOSED BUILDINGS, PROVIDED THE |
| AGGREGATE AREA OF THE GLAZING IN THE REPLACED |
| COMPONENTS DOES NOT EXCEED 25 PERCENT OF THE AGGREGATE |
| AREA OF THE GLAZED OPENINGS IN THE DWELLING OR DWELLING |
| UNIT. |
| |
| 2.OPENING PROTECTION EXCEPTION FOR HIGH-VELOCITY |
| HURRICANE ZONES: FOR ONE- AND TWO-FAMILY DWELLINGS |
| CONSTRUCTED UNDER CODES PRIOR TO SEPTEMBER 1, 1994 THE |
| REPLACEMENT OF EXTERIOR DOORS WITH GLAZING, SLIDING |
| GLASS DOORS, GLASS PATIO DOORS, SKYLIGHTS, AND OPERABLE |
| AND INOPERABLE WINDOWS WITHIN ANY 12 MONTH PERIOD SHALL |
| NOT BE REQUIRED TO HAVE OPENING PROTECTION PROVIDED THE |
| AGGREGATE AREA OF THE GLAZING IN THE REPLACED |
| COMPONENTS DOES NOT EXCEED 25 PERCENT OF THE AGGREGATE |
| AREA OF THE GLAZED OPENINGS IN THE DWELLING OR DWELLING |
| UNIT |
| |
| |