2018-02-28 07:43:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #18021157
 2/28/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THERE ARE DISCREPANCIES BETWEEN THE ORIGINAL FAN
 SCHEDULE SHOWN IN THE APPROVED GARAGE PLANS UNDER
 PERMIT #07090764 AND THE FAN SUBMITTAL DOCUMENTS: A)
 EF-20 DOES NOT MATCH IN ELECTRICAL VOLTAGE. THE
 SCHEDULE INDICATES 277/1, HOWEVER THE SUBMITTAL
 INDICATES 115/1. B) EF-21 IS A 3/4 HP IN THE SCHEDULE,
 BUT LISTED AS A 1/2 HP IN YOUR SUBMITTAL.
  
 2) THE SCOPE IOF WORK FOR CO2 SENSOR REPLACEMENTS NEEDS
 TO BE CLARIFIED. THERE ARE APPROXIMATELY 62 SENSORS IN
 THE EXISTING GARAGE, HOWEVER THE CONTRACT INDICATES
 ONLY 16 TO BE REPLACED. PLEASE NOTE THAT THE THE
 ORIGINAL SENSORS PER PLAN WERE CO2, AND THE CODE AT THE
 TIME SET AUTOMATIC EXHAUST FAN OPERATION FOR CO2 AT 25
 PPM (PARTS PER MILLION).
  
 THE CURRENT CODE REQUIRES BOTH CO2 AND NO2 SENSORS. THE
 SUBMITTAL FROM HONEYWELL IS RECOMMENDING THAT TYPE OF
 MULTI-SENSOR FOR PARKING GARAGES.
  
 PLEASE VERIFY THAT THOSE WILL BE THE TYPE OF SENSORS TO
 BE INSTALLED, AND INDICATE AT WHAT PPM LEVEL(S) THE
 FANS WILL AUTO OPERATE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  